This guide is applicable to the DCL Ultra-Small Series actuators, with the following models:

  • DCL-02A

  • DCL-02B

  • DCL-02G

华易精巧系列执行器 DCL-02 配阀 | DCL-02 Actuator Valve

Common Faults and Troubleshooting Methods

 

FaultPossible CausesTroubleshooting Methods
Actuator does not open or close on initial start1. Incorrect wiringCheck the wiring according to the actuator’s wiring diagram.
 2. Incorrect power supplyEnsure the power supply voltage is within ±10% of the actuator’s rated voltage and the current is 3 times the rated current.
 3. Faulty control switch or relayMeasure the input voltage at the actuator’s control terminal using a multimeter to verify it matches expectations.
 4. Control system mismatchTest the actuator with a mechanical switch. If it operates normally, verify the control system’s output logic.
 5. Multiple actuators or actuators and other devices connected in parallelSwitch actuators should use single-path control and not be wired in parallel, as this affects the startup capacitor.
Actuator can only open or close1. Incorrect wiringCheck the wiring using the actuator’s wiring diagram.
 2. Incorrect full open/close cam settingRefer to the “How to Set Electric Switch-Type Valves” guide and correctly set the cam positions.
Actuator stops in the middle of travel1. Valve jammedCheck for blockages in the valve. Clear any obstruction and retry after the actuator’s overload protection cools.
 2. Solid material in fluid causing valve jamInspect the fluid for solid particles causing valve jams. Clear the jam and retry after the actuator’s overload protection cools.
 3. Incorrect full open/close stopper settingRefer to the “How to Set Electric Switch-Type Valves” guide and correctly adjust the stopper positions.
Unable to turn actuator using the handle1. Solid material in fluid causing valve to seizeCheck for blockage in the valve. Clear the blockage and retry after the actuator’s overload protection cools.
 2. Valve seizingInspect the valve for jamming. Clear the blockage and retry after the actuator’s overload protection cools.
 3. Damaged actuator reduction mechanismRemove the actuator from the valve and rotate the handle. If it doesn’t move, replace the actuator.
No position feedback signal1. Incorrect wiring at the switchCheck the wiring according to the actuator’s wiring diagram.
 2. Incorrect full open/close cam settingRefer to the “How to Set Electric Switch-Type Valves” guide and set the cam position correctly.
 3. Overcurrent causing position feedback switch damage1. Check if the full open/close cam is pressing on the position feedback switch correctly, as per the guide.
  2. Measure if the position feedback circuit is closed.

 

Verify that the operating conditions meet the parameter requirements.

Electric actuators may fail due to improper use or being used in incorrect operating conditions. When used within the operating conditions defined in the product specifications, the actuator can be expected to operate reliably for an extended period without failure.

  • Supply Voltage: The voltage from the power supply must be within the rated operating voltage range of the actuator. Overvoltage or undervoltage may shorten the actuator’s lifespan.

  • Supply Current: The starting current of the motor is significantly higher than the rated current. To ensure reliable operation, use a power supply capable of delivering at least 3 times the rated current of the actuator.

  • Temperature: Ensure the actuator operates within its rated temperature range. Using the actuator outside this range may result in poor performance, reduced lifespan, and eventual failure.

  • Environment: The DCL switch-type actuator has an IP67 weatherproof rating, making it suitable for both indoor and outdoor applications. It offers a degree of protection against rain and splashing water, helping to prolong the actuator’s life by shielding it from rain, snow, ice, and UV (sunlight). However, in highly corrosive environments, electronic components may fail prematurely. Non-explosion-proof actuators should not be used in explosive environments.

  • Duty Cycle: The DCL switch-type actuator has a duty cycle of 70% (42 seconds of operation per minute, followed by 18 seconds of rest). Exceeding this duty cycle may cause the motor to enter thermal protection.

Check the Wiring of the Actuator

Ensure the actuator is wired correctly according to the wiring diagram provided by the manufacturer. Follow these steps to verify the wiring:

  1. Power Supply:

    • Check the power supply connections to ensure they match the actuator’s required input voltage and current.

  2. Control Connections:

    • Verify that the input and output control connections are securely attached and in the correct configuration as per the actuator’s wiring diagram.

  3. Signal Wiring:

    • Check the wiring for control signals, such as 4-20mA or 0-10V, depending on the actuator’s specifications.

    • Confirm that there are no loose connections or short circuits.

  4. Grounding:

    • Ensure that the actuator is properly grounded to prevent electrical interference or damage.

  5. Connections to Other Equipment:

    • If the actuator is connected to other devices, make sure those connections are also correct and do not cause interference or power issues.

If the wiring appears correct, but the actuator is still malfunctioning, further troubleshooting or assistance from a technician may be necessary.

A - Avec 2 sorties de signal de position finale actives

DCL 华易执行器A型接口图
  • Actionneur de commande pour ouvrir ou fermer avec K
  • La borne de sortie de la position finale OUVERTE/FERMÉE enverra l'événement sous la forme d'un signal actif de 220 V CA lorsque la position finale sera atteinte.

 

Détails de connexion :

  1. Raccordez le neutre de l'alimentation AC85-220V à P1.
  2. Mettez le commutateur de la ligne AC85-220V sur FERMÉ (P2) pour fermer la vanne.
  3. Mettez la ligne AC85-220V sur OUVERT (P3) pour ouvrir la vanne.
  4. P5 est une borne OPEN en position finale qui fournira une source AC220V pouvant être utilisée pour alimenter un voyant lumineux lorsque l'actionneur a atteint la position finale ouverte.
  5. P6 est une borne OUVERTE en position finale qui fournira une source de courant alternatif de 220 V pouvant être utilisée pour alimenter un voyant lumineux lorsque l'actionneur a atteint la position fermée.
  6. Reliez la terre à P7.

B - With 2 passive end-position switche

DCL 华易执行器B型接口图
  • Actionneur de commande pour ouvrir ou fermer avec K
  • La borne de sortie de la position finale OUVERTE/FERMÉE enverra l'événement sous forme de signal passif lorsque la position finale sera atteinte.

 

Détails de connexion :

  1. Raccordez le neutre de l'alimentation AC85-220V à P1.
  2. Mettez le commutateur de la ligne AC85-220V sur FERMÉ (P2) pour fermer la vanne.
  3. Mettez la ligne AC85-220V sur OUVERT (P3) pour ouvrir la vanne.
  4. P4 est le COM pour le signal de contact passif de position finale OUVERT/FERMÉ qui est normalement connecté au signal GND.
  5. P5 est la borne OPEN de fin de course qui sera connectée à COM lorsque l'actionneur atteindra la position d'ouverture finale.
  6. P6 est la borne de fermeture de fin de course qui sera connectée à COM lorsque l'actionneur atteindra la position de fermeture finale.
  7. Reliez la terre à P7.

Moteur à courant continu G avec 2 interrupteurs de fin de course

DCL 华易执行器G型接口图
  • Actionneur de commande pour s'ouvrir ou se fermer en fonction du sens d'alimentation entre les bornes 1 et 2
  • La borne de sortie de la position finale OUVERTE/FERMÉE enverra l'événement sous forme de signal passif lorsque la position finale sera atteinte.

 

Détails de connexion :

  1. Connecter le DC24V+ à P1 et le DC24V- à P2 pour fermer la vanne.
  2. Connecter DC24V+ à P2 et DC24V- à P1 pour fermer la vanne.
  3. P3 est le COM pour le signal de contact passif de position finale OUVERT/FERMÉ qui est normalement connecté au signal GND.
  4. P4 est la borne OPEN de fin de course qui sera connectée à COM lorsque l'actionneur atteindra la position d'ouverture finale.
  5. P5 est la borne de fermeture en fin de course qui sera connectée à COM lorsque l'actionneur atteindra la position de fermeture.
  6. Reliez la terre à P7.

Note:

  • Le circuit à l'intérieur du cadre en pointillés représente le circuit interne de l'actionneur. Le circuit extérieur illustre le branchement électrique nécessaire à l'utilisation de l'actionneur.
  • Si vous avez d'autres exigences spécifiques concernant le raccordement du circuit, n'hésitez pas à contacter notre assistance technique. 

When conducting troubleshooting on-site, feel free to contact our technical service personnel immediately for assistance in diagnosing and resolving the issue.
Contact phone number: 13026331611 (Mr. Chen)