DCL电动执行器可以驱动哪些阀门?

The DCL electric actuator is mainly used to drive butterfly valves with a diameter of less than 600mm, ball valves with a diameter of less than 350mm, and ventilation dampers and air flap valves with a diameter of less than 1200mm.

Beyond these applications, some interesting use cases are also worth noting. For example:

  • Rotating solar photovoltaic panels to track sunlight.
  • Controlling louvers for natural ventilation.
  • Driving specific baffles in certain scenarios using a linkage arm.

 

Applications of DCL Electric Actuator:

Driving Butterfly Valves

The DCL electric actuator can drive butterfly valves ranging from DN50 to DN600. Under normal operating conditions, the pipeline pressure should not exceed 1.0 MPa.

If the pipeline pressure exceeds 1.0 MPa, it is necessary to select an appropriate model based on the torque parameters of the valve. You can contact technical support to ensure the correct actuator model selection.

Butterfly Valve (Pressure ≤ PN1.0MPa)Rated Torque (Nm)Weather-Proof ActuatorExplosion-Proof Actuator
DN50~6550DCL-05DCL-Ex05
DN80~100100DCL-10DCL-Ex10
DN125~150200DCL-20DCL-Ex20
DN200400DCL-40DCL-Ex40
DN250600DCL-60DCL-Ex60
DN3001000DCL-100nothing
DN350~4001600DCL-160nothing
DN450~6002500DCL-250nothing

Driving Ball Valves

The DCL electric actuator can drive ball valves ranging from DN40 to DN350. Under normal operating conditions, the pipeline pressure should not exceed 1.0 MPa.

If the pipeline pressure exceeds 1.0 MPa, it is necessary to select an appropriate model based on the torque parameters of the valve. You can contact technical support to ensure the correct actuator model selection.

Ball Valve (Pressure ≤ PN1.6MPa)Rated Torque (Nm)Ordinary ActuatorsExplosion-Proof Actuator
DN4050DCL-05DCL-Ex05
DN50~65100DCL-10DCL-Ex10
DN80~100200DCL-20DCL-Ex20
DN125400DCL-40DCL-Ex40
DN150600DCL-60DCL-Ex60
DN2001000DCL-100nothing
DN2501600DCL-160nothing
DN300~3502500DCL-250nothing

Driving Ventilation Dampers and Air Flap Valves

he DCL electric actuator can drive ventilation dampers ranging from DN50 to DN1200. Under normal operating conditions, the pipeline pressure should not exceed 0.1 MPa.

If the pipeline pressure exceeds 0.1 MPa, it is necessary to select an appropriate model based on the torque parameters of the valve. You can contact technical support to ensure the

Vent Valve (Pressure ≤ PN0.1MPa)Rated torque (Nm)Weather-Proof ActuatorsExplosion-Proof Actuator
DN50-8050DCL-05DCL-Ex05
DN100-200100DCL-10DCL-Ex10
DN250-300200DCL-20DCL-Ex20
DN350-450400DCL-40DCL-Ex40
DN500-600600DCL-60DCL-Ex60
DN700-8001000DCL-100nothing
DN9001600DCL-160nothing
DN1000-12002500DCL-250nothing

The duct diameter, pressure, and friction coefficient affect the torque required to drive the ventilation damper. You can refer to the following table to determine the appropriate actuator torque for the damper.

Diameter (mm)Pressure (bar)friction coefficientTorque (kg-m)
200100.1523.15
200100.2527.86
250100.135.01
250100.1539.92
250100.2549.75
300100.159.51
300100.1567.47
300100.2583.38
350100.181.19
350100.1592.03
350100.25113.69
400100.1109.49
400100.15120.49
400100.25156.65
450100.1149.8
450100.15170.83
450100.25218.58
500100.15266.22
500100.25335
550100.1287.24
550100.15331.82
550100.25420.98
600100.1355.09
600100.15406.52
600100.25519.71
650100.1449.33
650100.15503.95
650100.25631.98
700100.1586.7
700100.15678.17
700100.25861.11
800100.1819.51
800100.15940.67
800100.251192.31
900100.11186.13
900100.151327.81
900100.251611.15
100060.1996.28
100060.151095.75
1000100.11603.41
1000100.151763.11
1000100.252150.94
110060.11396.38
110060.151574.71
110060.251931.35
1100100.12126.78
1100100.152366.02
1100100.252875.61
120060.11703.89
120060.151915.73
120060.252357.15
1200100.12753.18
1200100.153059.8
1200100.253673.03
130060.12151.23
130060.152326.25
130060.252836.89
1300100.13543.27
1300100.153954.52
1300100.254777.03
140060.12670.64
140060.152881.14
140060.253373.82
1400100.14441.51
1400100.154963.18
1400100.256006.53
150060.13383.88
150060.153781.8
150060.254577.62
1500100.15548.41
1500100.156232.82
1500100.257689.31
160060.13986.5
160060.154432.28
1600100.16785.63
1600100.157642.21
1600100.259379.74
180060.15676.09
180060.156123.48
1800100.2513140.31
200060.18139.04
200060.159176.55
200060.2511251.6
2000100.113070.69
2000100.1514652.43
2000100.2517815.93
220060.110437.6
220060.1511474.04
220060.2514098.96
2200100.117308.75
2200100.2523492.16
240060.113454.44
240060.1514514.93
240060.2517378.15
2400100.122375.98
2400100.1525004.03
2400100.2530260.3
260060.117040.2
260060.1519032.71
260060.2523017.73
2600100.128346.48
2600100.1531636.21
2600100.2538216.28
280060.121124.58
280060.1522765.63
280060.2527572.18
2800100.135293.63
2800100.1539347.76
2800100.2547456.04
300060.125863.96
300060.1527728.1
300060.2532693.85
3000100.143292.29
3000100.1548220.04
3000100.2558075.54

Driving Other Types of Valves

In addition to standard applications, the DCL electric actuator can also drive three-way valves and other part-turn valves.

You can contact technical support to select the appropriate type and model of the electric actuator for your specific needs.

Driving Other Devices

  • Rotating solar photovoltaic panels for sunlight tracking.
  • Controlling louvers for natural ventilation.
  • Driving baffles using a swing arm mechanism.