DCL Actuator with FSR

Operation Panel

  • Connection

    P1:DC24V Power +

    P3:DC24V Power –

    P5:4-20mA Input –

    P7:4-20mA Input +

    P9:4-20mA Output –

    P11:4-20mA Output +

    P2:ON/OFF Input COM

    P4:ON/OFF Input Open

    P6:ON/OFF Input Close

    P8:ON/OFF Output COM

    P10:ON/OFF Output Open

    P12:ON/OFF Output Close

  • Button

    KO: Used in setting mode. Press this button to open the actuator
    while release it to stop. Press “Set” and “Open” simultaneously to
    set the full open position.

    KC: Used in setting mode. Press this button to Shut the actuator
    while release it to stop. Press “Set” and “Shut” simultaneously to
    set the full shut position.

    KS: Used in setting mode. Combination use this button with
    others to configure the parameters.

  • Switch

    SA: Set operation mode (Default set to 1):

1–Normal Modulation 2–Setting Mode 3–Reverse Modulation

SB: Set Safety Position (Default set to 1):

1–Drive to Fully Open 2–Keep Position 3–Drive to Fully
Shut

  • Indication

    L1: Green, Power Indication;

    L2: Red, Input signal error, turned on when input signal is over
    range;

    L3: Red, Potentiometer error, turned on when potentiometer is
    abnormal or connection wire is broken;

    L4: Red, Stuck error, turned on when actuator can not be driven
    to open or close.

Settings

Switch SA to 2 to enter the setting mode. Then you can set the
operation rotation range, set the safety position, calibrate the input
and output signal and etc.

  • Operation Range

    Configure Fully Close Position

  1. Press the Open/Shut button to drive the valve to the fully closed
    position.
  2. Hold the Set button and then the Shut button until L2 is turned on
    about 3-4 seconds later which means the fully closed position
    configuration is done.
  3. Now you can release these 2 buttons.

    Configure Fully Open Position

  1. Press the Open/Shut button to drive the valve to the fully open
    position.
  2. Hold the Set button and then the Open button until L2 is turned on
    about 3-4 seconds later which means the fully open position
    configuration is done.
  3. Now you can release these 2 buttons.

    [Note: When the fully open and close position was configured with
    the same position, the configuration will be done successfully. But
    the actuator will not rotate in modulation mode.]{.underline}

  • Set Safety Position

Set the safety position with SB as you wish when supply power was broken
down or input signal was fault.

  • Turn S-B to 1 to let the actuator drive the valve to fully open
    position.
  • Turn S-B to 2 to let the actuator keep the current valve position.
  • Turn SB to 3 to let the actuator drive the valve to fully close
    position.

    This part of configuration is normally unnecessary, reconfigure
    these if it really matters.

  • 4-20mA Output Calibration
  1. Turn S-A to 2
  2. Connect an ammeter to signal output to monitor current.
  3. Hold the set button then open and shut simultaneously until L2 is
    turned on which means 4mA calibration mode being entered. Now you
    could release these 3 buttons.
  4. Press Open(increase) or Shut(decrease) to adjust 4mA.
  5. Hold the set button until L2 was turned off and on again, then
    release the button to enter 20mA calibration.
  6. Press Open(increase) or Shut(decrease) to adjust 20mA.
  7. Hold the set button until L2 was turned off and on again, then
    release the button to complete the calibration process.
  • 4-20mA Input Calibration
  1. Turn S-A to 2
  2. Connect a 4-20mA current source to signal input to generate a
    reference.
  3. Hold the Set button until L2 start blinking, release Set. Hold Open
    and Shut simultaneously until L3 start blinking which indicate
    calibration mode being entered, now release these 2 buttons.
  4. Generate a 4ma reference to Input, Hold the set then shut until L4
    is turned on which indicates the current input was calibrated as a
    4mA reference. You could release the 2 buttons now.
  5. Generate a 20ma reference to Input, Hold the Set then Shut until L4
    is turned on which indicates the current input was calibrated as the
    20mA reference. You could release the 2 buttons now.
  6. Hold Set until L3 stop blinking which indicates calibration being
    completed.

Start to Use

  • Modulation with 4-20mA

Turn S-A to 1 to start modulation.

  • The actuator will drive the valve to the specific position as the
    4-20mA input signal assigned。
  • The 4-20mA output signal will output the valve position in real
    time.
  • The “ON/OFF Output Open” will output a signal(connect to COM) when
    the valve was driven to the full open position.
  • The “ON/OFF Output Shut” will output a signal(connect to COM) when
    the valve was driven to the full close position.
  • The actuator will drive the valve to the safety position when supply
    power was broken down or input signal was fault.
  • The actuator will return to modulation mode after supply power and
    input signal was recovered.

    [Note: You can turn S-A to 3 to activate the reverse operation. In
    which, 4mA input value will be transferred as 20mA, and 20mA will be
    transferred as 4mA. So the modulation is just like
    reversed.]{.underline}

    1714094198309{width=”6.720833333333333in”
    height=”1.070138888888889in”}

  • ON/OFF with Passive Digital Input

Turn S-A to 1 to start modulation.

  • The actuator will drive the valve to the fully open position when
    the “ON/OFF Output Open” was effective(connect to COM).
  • The actuator will drive the valve to the fully close position when
    the “ON/OFF Output Close” was effective(connect to COM).
  • The “ON/OFF Output Open” will output a signal(connect to COM) when
    the valve was driven to the full open position.
  • The “ON/OFF Output Shut” will output a signal(connect to COM) when
    the valve was driven to the full close position.
  • The 4-20mA output signal will output the valve position in real
    time.
  • The actuator will drive the valve to the safety position when supply
    power was broken down.
  • The actuator will return to modulation mode after supply power was
    recovered.

  • Modulation with Modbus-RTU/RS485

Contact us to get more details…

Fault Indication

  • L2: Input Signal Error

    Input signal is break or go out of the range(<2.5mA or > 21.5mA)

  • L3: Position Measurement Error

    Potentiometer or connection wire is broken

  • L4: Stuck Error

    The valve was stuck and actuator can not drive the valve to the
    expected position.