Setting the hysteresis allows the actuator to better match PID closed-loop control applications.
Steps to Set the Hysteresis:
Turn the S-A switch (highlighted in the red box below) to position 2.
Rotate the adjustment knob (highlighted in the yellow box) to set the hysteresis.
Each scale mark represents 0.5%.
The adjustable hysteresis range is 0.5% to 5%.