| Model | Zwenkhoek | Torque/Operating Time | Duty Type | Voedingsspanning | Input/Output Signal | Extra opties |
|---|---|---|---|---|---|---|
| DCL-05 | 0 - 360° | 50Nm/20s Optioneel met 20Nm/4s 30Nm/10s 50Nm/60s | AAN - UIT Modulerend Inch bewegen - Positioneren | DC24V AC24V AC110V AC220V AC380V | 4-20mA 0-10V IO Interface Optional with field bus Modbus-RTU Modbus-ASCII CAN Ethernet | Over torque protection Fail Safe Return Ontvochtiging Veldbus |
| DCL-10 | 0 - 360° | 100Nm/30s Optioneel met 20Nm/4s 30Nm/10s 50Nm/60s | AAN - UIT Modulerend Inch bewegen - Positioneren | DC24V AC24V AC110V AC220V AC380V | 4-20mA 0-10V IO Interface Optional with field bus Modbus-RTU Modbus-ASCII CAN Ethernet | Over torque protection Fail Safe Return Ontvochtiging Veldbus |
| DCL-20 | 0 - 90° | 200Nm/30s Optioneel met 100Nm/15s 200Nm/60s | AAN - UIT Modulerend Inch bewegen - Positioneren | DC24V AC24V AC110V AC220V AC380V | 4-20mA 0-10V IO Interface Optional with field bus Modbus-RTU Modbus-ASCII CAN Ethernet | Over torque protection Fail Safe Return Ontvochtiging Veldbus |
| DCL-40 | 0 - 90° | 400Nm/30s Optioneel met 200Nm/15s 400Nm/60s | AAN - UIT Modulerend Inch bewegen - Positioneren | DC24V AC24V AC110V AC220V AC380V | 4-20mA 0-10V IO Interface Optional with field bus Modbus-RTU Modbus-ASCII CAN Ethernet | Over torque protection Fail Safe Return Ontvochtiging Veldbus |
| DCL-60 | 0 - 90° | 600Nm/45s | AAN - UIT Modulerend Inch bewegen - Positioneren | DC24V AC24V AC110V AC220V AC380V | 4-20mA 0-10V IO Interface Optional with field bus Modbus-RTU Modbus-ASCII CAN Ethernet | Over torque protection Fail Safe Return Ontvochtiging Veldbus |
| DCL-100 | 0 - 90° | 1000Nm/30s Optioneel met 500Nm/15s | AAN - UIT Modulerend Inch bewegen - Positioneren | AC110V AC220V AC380V | 4-20mA 0-10V IO Interface Optional with field bus Modbus-RTU Modbus-ASCII CAN Ethernet | Over torque protection Fail Safe Return Ontvochtiging Veldbus |
| DCL-160 | 0 - 90° | 1600Nm/48s | AAN - UIT Modulerend Inch bewegen - Positioneren | AC110V AC220V AC380V | 4-20mA 0-10V IO Interface Optional with field bus Modbus-RTU Modbus-ASCII CAN Ethernet | Over torque protection Fail Safe Return Ontvochtiging Veldbus |
| DCL-250 | 0 - 90° | 2500Nm/75s | AAN - UIT Modulerend Inch bewegen - Positioneren | AC110V AC220V AC380V | 4-20mA 0-10V IO Interface Optional with field bus Modbus-RTU Modbus-ASCII CAN Ethernet | Over torque protection Fail Safe Return Ontvochtiging Veldbus |
Recommend actuator to drive a butterfly valve
Recommend actuator to drive a Ball valve
Recommend actuator to drive a ventilation valve
Recommend valve to be driven by DCL weather-proof actuator
| Model | Torque (Nm) | Butterfly Valve (≤ PN1.0MPa) | Ball Valve (≤ PN1.6MPa) | Ventilation Valve (≤ PN0.1MPa) |
|---|---|---|---|---|
| DCL-05 | 50 | DN50~65 | DN40 | DN50~80 |
| DCL-10 | 100 | DN80~100 | DN50~65 | DN100~200 |
| DCL-20 | 200 | DN125~150 | DN80~100 | DN250~300 |
| DCL-40 | 400 | DN200 | DN125 | DN350~450 |
| DCL-60 | 600 | DN250 | DN150 | DN500~600 |
| DCL-100 | 1000 | DN300 | DN200 | DN700~800 |
| DCL-160 | 1600 | DN350~400 | DN250 | DN900 |
| DCL-250 | 2500 | DN450~600 | DN300~350 | DN1000~1200 |
Note: The recommendations in the above table is for reference only in common application scenario, the specific torque needed to drive the valve is depended up on the real application case.
It is recommended to choose an actuator with 1.1-1.3 times of torque than the value that was finalized after evaluation of torque requirement of valve and liquid pressure in the pipe. This would improve the robust performance in most worst case.