The DC-FB3 module, when installed in the DCL electric actuator, allows for controlling the valve’s position using Modbus-TCP/IP. The installation is shown below:

DC-FB3

 

DC-FB3 Installed into the DCL Actuator

1. Controlling DCL Electric Actuator via Modbus-TCP/IP Using Default Parameters

The DC-FB3 is pre-configured in Client mode. Using the default MAC, IP, Gateway, Server, and Port parameters, you can control the DCL electric actuator via Modbus-TCP/IP. The default parameters are indicated within the blue box in the image below.

When using the default parameters, you can skip step 2 and proceed directly to step 3, using Modbus-TCP/IP to control the DCL electric actuator.

DCL Modbus TCP/IP Actuator

2. Changing TCP/IP Network Parameters

2.1 Connect DC-FB3 to PC Using DC-FB1 (USB to RS485)

Connecting DCL Actuator with Modbus TCP/IP to Computer

The wiring for connecting the DC-FB3 is as follows:

  • Red Box 1: Connect to AC220V power supply.

  • Green Box 4: Connect to the RS485 interface (A/B) of DC-FB1.

  • DC-FB1 USB: Plug into the PC.

For further details, refer to the DC-FB1 user manual.

 

2.2 Use Configuration Software on PC to Set Network Parameters

Download Configuration Software: Install the necessary configuration software for setting the network parameters.

Select Correct Port: Open the configuration software, choose the correct port, and click CONNECT to connect to DC-FB3.

Once connected, the configuration software will automatically read the parameters from the DC-FB3.

Change Network Parameters: After modifying the network parameters, click SAVE to store the updated parameters in the DC-FB3.

3. Control DCL Actuator through Modbus-TCP/IP

Hardware connections

  • Connect AC220V power supply to terminals marked with red box 1
  • Insert RJ45 plug into socket marked with yellow box 2

Now you can control actuator through modbus-RTU commands following the DCL Actuator Modbus Application Manual

Lær mer