Products

Technical Parameters

Power SupplyAC110V, AC220V, AC380V
Standard Torque/Time1600Nm/48S
Rotation Angle RangeAdjustable from 0 to 90 degrees
Motor powerAC110V:140W/1.75A
AC220V:140W/0.96A
AC380V:100W/0.46A
Control CircuitType A/B/C/D/E/F/H
Weight19.5Kg
Insulation Resistance AC110V/AC220V/AC380V: 100MΩ/500VDC
Withstand VoltageAC110V/AC220V: 1500VAC for 1 minute
Water Proof LevelIP67
Installation360 ° installation at any angle
Electrical InterfaceG1/2 waterproof cable connector: one power line and one signal line each
Working Temperature-25℃ ~ +55℃
Optional FunctionOver torque protection, dehumidification heater, convex indicator, operating handwheel
Modulation Parameters
Segnale di ingresso4~20mA, 0~10V arbitrary calibration
output Signal4~20mA, 0~10V arbitrary calibration
Bus485/Modbus/CAN
Internet of ThingsWIFI/LoRA/4G
Basic Error≤±1%
Return Error≤1%
HysteresisAdjustable from 0.5% to 5.0%
Reposition Times0 times
Repeatability Error≤1%

Dimensions

华易普通型执行器安装形式 | DCL Electrical Actuator Install Type
华易电动执行器 DCL-100 DCL-160 DCL-250 外型安装尺寸

Application Circuit

Modulazione

E - Modulazione con un'unità di controllo

  • Ingresso: 4~20mA / 0~10V
  • Uscita: 4~20mA / 0~10V
  • Field Bus:Modbus / CAN
  • IIot:WIFI/LoRA/4G DTU

 

Dettagli di connessione:

  1. Collegare la linea di alimentazione CA 85-220V al terminale L e il neutro al terminale N.
  2. Collegamento della sorgente di segnale di ingresso 4-20mA/2-10V dal sistema di controllo all'ingresso-/+.
  3. Collegare l'uscita +/- al sistema per inviare la posizione della valvola in tempo reale.

Inching and positioning

F - With a positioning unit

  • Control actuator to open or close with K
  • The real-time valve position will be send out as a 4-20mA signal.

 

Dettagli di connessione:

  1. Collegare la linea di alimentazione CA 85-220V al terminale L e il neutro al terminale N.
  2. Switch AC85-220V line to CLOSE(P2) to close the valve.
  3. Switch AC85-220V line to OPEN(P3) to open the valve.
  4. Collegare l'uscita +/- al sistema per inviare la posizione della valvola in tempo reale.

C - With a 1KΩ/500Ω potentiometer

  • Control actuator to open or close with K
  • The real-time valve position will be send out as a potentiometer resistance value

 

Dettagli di connessione:

  1. Connecting AC85-220V supply power neutral to P1.
  2. Switch AC85-220V line to CLOSE(P2) to close the valve
  3. Switch AC85-220V line to OPEN(P3) to open the valve.
  4. P4 is the low side of potentiometer that is normally connected to signal GND.
  5. Connecting signal input of  control system to P5. The resistance value between P4 and P5 will become higher as actuator opening the valve, while the value between P5 and P6 will become lower.
  6. P6 is the high side of potentiometer that is normally connected to signal power.
  7. Connect earth to P7.

D - With a potentiometer and end-position feedback

  • Control actuator to open or close with K
  • The real-time valve position will be send out as a potentiometer resistance value
  • The output terminal of end-position OPEN/CLOSE will send out the event as a passive signal form when the end-position was reached.

 

Dettagli di connessione:

  1. Connecting AC85-220V supply power neutral to P1.
  2. Switch AC85-220V line to CLOSE(P2) to close the valve
  3. Switch AC85-220V line to OPEN(P3) to open the valve.
  4. P4 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
  5. P5 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
  6. P6 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
  7. P7 is the low side of potentiometer that is normally connected to signal GND.
  8. Connecting signal input of  control system to P8. The resistance value between P7 and P8 will become higher as actuator opening the valve, while the value between P8 and P9 will become lower.
  9. P9 is the high side of potentiometer that is normally connected to signal power.
  10. Connect earth to P12.

ON - OFF

A - With 2 active end-position signal outputs

  • Control actuator to open or close with K
  • The output terminal of end-position OPEN/CLOSE will send out the event as a 220VAC active signal form when the end-position was reached.

 

Dettagli di connessione:

  1. Connecting AC85-220V supply power neutral to P1.
  2. Switch AC85-220V line to CLOSE(P2) to close the valve
  3. Switch AC85-220V line to OPEN(P3) to open the valve.
  4. P5 is end-position OPEN terminal which will output a AC220V source which can be used to drive an Indication light when actuator reached end-position of open.
  5. P6 is end-position OPEN terminal which will output a AC220V source which can be used to drive an Indication light when actuator reached end-position of close.
  6. Connect earth to P7.

B - With 2 passive end-position switches

  • Control actuator to open or close with K
  • The output terminal of end-position OPEN/CLOSE will send out the event as a passive signal form when the end-position was reached.

 

Dettagli di connessione:

  1. Connecting AC85-220V supply power neutral to P1.
  2. Switch AC85-220V line to CLOSE(P2) to close the valve
  3. Switch AC85-220V line to OPEN(P3) to open the valve.
  4. P4 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
  5. P5 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
  6. P6 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
  7. Connect earth to P7.

G - DC motor with 2 end-position switches

  • Control actuator to open or close by the supply power direction between the terminal 1 and 2
  • The output terminal of end-position OPEN/CLOSE will send out the event as a passive signal form when the end-position was reached.

 

Dettagli di connessione:

  1. Connecting DC24V+ to P1 and DC24V- to P2 to close the valve.
  2. Connecting DC24V+ to P2 and DC24V- to P1 to close the valve.
  3. P3 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
  4. P4 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
  5. P5 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
  6. Connect earth to P7.

H - 3 phase 380VAC motor with 2 end-position switches

  • Control actuator to open or close by an external inverter to change the phase of supply power.
  • The output terminal of end-position OPEN/CLOSE will send out the event as a passive signal form when the end-position was reached.

 

Dettagli di connessione:

  1. Connecting a 3 phase AC380V inverter output to P1, P2 and P3, then the actuator can be controlled to open or close the valve by change the 3 phase order.
  2. Connecting AC380V neutral to N(P4).
  3. P5 is used for cooperating with an external switch to control the inverter 3 phase order. This terminal is connected to N(P4) when actuator is not in end-position of CLOSE and disconnected from N(P4) after actuator reached end-position of CLOSE.
  4. P6 is used for cooperating with an external switch to control the inverter 3 phase order. This terminal is connected to N(P4) when actuator is not in end-position of OPEN and disconnected from N(P4) after actuator reached end-position of OPEN.
  5. P7 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
  6. P8 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
  7. P9 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
  8. Connect earth to P12.

Nota:

  • Il circuito all'interno del riquadro tratteggiato è il circuito interno dell'attuatore. Il circuito esterno, invece, mostra lo schema di collegamento elettrico per il funzionamento dell'attuatore.
  • Se avete altre esigenze specifiche riguardo al circuito di collegamento, non esitate a contattare il nostro supporto tecnico. 

Choose another actuator with different torque​

50 Nm/20 secondi

————————–

Opzionale con

20 Nm/4S

30 Nm/10 s

50 Nm/60 secondi

50 Nm/100 s

100 Nm/30 secondi

————————–

Opzionale con

50 Nm/15S

100 Nm/60 secondi

 

 

200 Nm/30 secondi

————————–

Opzionale con

100 Nm/15S

200 Nm/60 secondi

 

 

400 Nm/30 secondi

————————–

Opzionale con

200 Nm/15S

400 Nm/60 secondi

 

 

Richiesta di preventivo

Premi "Invia" ora, in seguito ti confermeremo il numero di modello del prodotto e il distributore locale e poi ti invieremo il preventivo.

Bomba

Scansiona il codice QR per chattare subito con un nostro tecnico...

Richiesta di preventivo

Premi "Invia" ora, in seguito ti confermeremo il numero di modello del prodotto e il distributore locale e poi ti invieremo il preventivo.

Bomba

Scansiona il codice QR per chattare subito con un nostro tecnico...

Richiesta di preventivo

Premi "Invia" ora, in seguito ti confermeremo il numero di modello del prodotto e il distributore locale e poi ti invieremo il preventivo.

Bomba

Scansiona il codice QR per chattare subito con un nostro tecnico...

🤝 Costruiamo insieme il tuo brand

✅ ODM

  • Il tuo logo e il tuo packaging
  • Formati di uscita personalizzati (4-20 mA, RS485 Modbus, HART, ecc.)
  • Modifiche al colore dell'involucro o all'etichetta
  • Versioni compatibili con il cloud (opzionali)

✅ OEM

  • Attenersi scrupolosamente al progetto e alle specifiche
  • Massima riservatezza e protezione della proprietà intellettuale.
  • Produzione di alta qualità a costi competitivi
  • Produzione in piccoli lotti o su larga scala
  • 🏭 Ricerca e sviluppo e produzione interneDalla scheda PCB all'involucro, tutto sotto lo stesso tetto.
  • 💬 Supporto multilingue: Ingegneri e personale di vendita che parlino inglese.

  • ⚙️ Quantità minima d'ordine flessibileSupporto sia per le startup che per i marchi globali.

  • 🚀 Prototipazione rapidaConsegna dei campioni in 7-10 giorni.

 Contattaci oggi stesso per richiedere un catalogo prodotti o per ottenere una consulenza gratuita.

Richiesta di preventivo

Invia richiesta

Bomba

Scansiona il codice QR per chattare subito con un nostro tecnico...

Contattaci

Telefono

(+86) 130 2633 1611

Bomba

Ken Bryan

即时客服图标 | Icona del messaggio in tempo reale

Chat in loco

Clicca sull'icona in basso a destra per chattare con noi...