Technical Parameters
Range | 0 ~ 200m(H2O) |
Accuracy | 0~2m(H2O) : ±0.5% 2~7m(H2O) : ±0.25% 7~200m(H2O) : ±0.1% |
Long-term Stability | ≤± 0.2%/year |
Overload Pressure | 2 times the full-scale pressure |
Supply Voltage | 9 ~ 30VDC |
output Signal | 4~20mA; 0~5V/10V; Modbus |
Working Temperature | -20~70 ℃ (cable material: polyethylene, polyvinyl chloride) |
Storage Temperature | -20 ~ 85℃ |
Vibration | 20g, 20 ~ 2000Hz |
Shock | 20g, 11ms |
Water Proof Level | IP68 |
Weight | ≤250g |
Dimensions

Materials
Isolation Membrane: Stainless Steel 316L / Tantalum
Shell: Stainless Steel 304 / Stainless Steel 316L
Wire: Polyethylene / Polyurethane / Polyvinyl chloride.
Installation
Direct Installation

Installation with a junction box features waterproof and EMI protection

Electric Diagram
4-20mA with 2 wires

4~20mA (3线制)

液位+温度 (4~20mA, 2线制)

RS485 · Modbus_RTU · ASCII

load capacity
4~20mA : ≤ (U-10)/0.02 (Ω)
RS485 : 99communications node