Compare parameters between DCL explosion-proof actuators
| Model | Ângulo de oscilação | Torque/Tempo de Operação | Duty Type | Tensão de alimentação | Sinal de entrada/saída | Additional Option |
|---|---|---|---|---|---|---|
| DCL-Ex05 | 0 - 360 ° | 50 Nm/20 S Opcional com 20 Nm/4 S 30 Nm/10 S 50 Nm/60 S | LIGADO - DESLIGADO Modulação Posicionamento gradual - Posicionamento | 24 VCC AC24V AC110V AC220V AC380V | 4-20mA 0-10V Interface de E/S Optional with field bus Modbus-RTU Modbus-ASCII CAN Ethernet | Over torque protection Retorno à prova de falhas Desumidificação Ônibus de campo |
| DCL-Ex10 | 0 - 90 ° | 100 Nm/30 S Opcional com 50 Nm/15 S 100 Nm/60 S | LIGADO - DESLIGADO Modulação Posicionamento gradual - Posicionamento | 24 VCC AC24V AC110V AC220V AC380V | 4-20mA 0-10V Interface de E/S Optional with field bus Modbus-RTU Modbus-ASCII CAN Ethernet | Over torque protection Retorno à prova de falhas Desumidificação Ônibus de campo |
| DCL-Ex20 | 0 - 90 ° | 200 Nm/30 S Opcional com 100 Nm/15 S 200 Nm/60 S | LIGADO - DESLIGADO Modulação Posicionamento gradual - Posicionamento | 24 VCC AC110V AC220V AC380V | 4-20mA 0-10V Interface de E/S Optional with field bus Modbus-RTU Modbus-ASCII CAN Ethernet | Over torque protection Retorno à prova de falhas Desumidificação Ônibus de campo |
| DCL-Ex40 | 0 - 90 ° | 400 Nm/30 S Opcional com 200 Nm/15 S 400 Nm/60 S | LIGADO - DESLIGADO Modulação Posicionamento gradual - Posicionamento | 24 VCC AC110V AC220V AC380V | 4-20mA 0-10V Interface de E/S Optional with field bus Modbus-RTU Modbus-ASCII CAN Ethernet | Over torque protection Retorno à prova de falhas Desumidificação Ônibus de campo |
| DCL-Ex60 | 0 - 90 ° | 600 Nm/45 S | LIGADO - DESLIGADO Modulação Posicionamento gradual - Posicionamento | 24 VCC AC110V AC220V AC380V | 4-20mA 0-10V Interface de E/S Optional with field bus Modbus-RTU Modbus-ASCII CAN Ethernet | Over torque protection Retorno à prova de falhas Desumidificação Ônibus de campo |
Recommend actuator to drive a butterfly valve
Recommend actuator to drive a Ball valve
Recommend actuator to drive a ventilation valve
Recommend valve to be driven by DCL explosion-proof actuator
Note: The recommendations in the above table is for reference only in common application scenario, the specific torque needed to drive the valve is depended up on the real application case.
It is recommended to choose an actuator with 1.1-1.3 times of torque than the value that was finalized after evaluation of torque requirement of valve and liquid pressure in the pipe. This would improve the robust performance in most worst case.
View actuators with different torque
50 Nm/20 S
————————–
Opcional com
20 Nm/4 S
30 Nm/10 S
50 Nm/60 S
100 Nm/30 S
————————–
Opcional com
50 Nm/15 S
100 Nm/60 S
200 Nm/30 S
————————–
Opcional com
100 Nm/15 S
200 Nm/60 S
400 Nm/30 S
————————–
Opcional com
200 Nm/15 S
400 Nm/60 S