1、Common malfunctions and troubleshooting methods.

fault가능한 이유Exclusion method
액추에이터는 초기 시동 중에 열리거나 닫히지 않습니다.1. 잘못된 배선액추에이터의 배선도에 따라 배선이 올바른지 확인하시겠습니까?
2. 잘못된 전원 공급 장치전원 공급 장치의 출력 전압이 액추에이터 정격 전압의 ± 10%이고 출력 전류가 액추에이터 정격 전류의 3배인지 확인합니다.
3. SA is not set to level 1 or 3Check and set SA to either 1st or 3rd gear.
4. Emergency stop switch disconnected (for actuators equipped with emergency stop function)Check and turn on the emergency stop switch.
5. Input Signal exceeds the RangeUse a multimeter to measure the voltage between control modules P3 and P4, and verify if the voltage is within the following Range:
6. Set the fully open and fully closed positions to the same position.다음을 참조하세요."How to set up a regulating electric valve Travel calibrationsection, correctly set the fully open/fully closed position.
The actuator stops before running to the target position1. 밸브 고착밸브 고착 여부를 확인하고, 고착을 제거한 후 액추에이터 과부하 보호 냉각 후 다시 시도합니다.
2. 유체 매체에 잠재적인 고체 물질이 있으면 밸브 막힘이 발생할 수 있습니다.유체 매체의 밸브에 고체 물체가 끼어 있는지 확인하고, 끼어 있는 밸브를 제거한 다음 액추에이터 과부하 보호 기능이 식은 후 다시 시도합니다.
3. Setting the fully open or fully closed position to the middle position is incorrect.다음을 참조하세요."How to set up a regulating electric valve Travel calibrationsection, correctly set the fully open/fully closed position.
4. Incorrect calibration of input signal Range.다음을 참조하세요."How to set up a regulating electric valve Input Signal calibrationsection, correctly calibrate the input signal Range.
핸들을 사용하면 액추에이터를 회전할 수 없습니다.유체 매체의 잠재적인 고체 물질은 밸브 막힘을 유발할 수 있습니다.유체 매체의 밸브에 고체 물체가 끼어 있는지 확인하고, 끼어 있는 밸브를 제거한 다음 액추에이터 과부하 보호 기능이 식은 후 다시 시도합니다.
2. 밸브 고착밸브 고착 여부를 확인하고, 고착을 제거한 후 액추에이터 과부하 보호 냉각 후 다시 시도합니다.
3. 액추에이터 감속 메커니즘이 손상되었습니다.밸브에서 액추에이터를 제거하고 핸들을 돌립니다. 회전이 되지 않으면 새 액추에이터로 교체합니다.
The feedback signal is incorrect1. Open circuit of the circuitMeasure the voltage between control modules P5 and P6 with a multimeter. If the measured value is>18V, it indicates an open circuit signal. Check and repair any wiring issues.
2. The input impedance of the feedback signal receiving end is too high.Measure and confirm that the input impedance of the feedback signal receiving end is less than 800 ohms
3. Feedback signal calibration error.1. Refer to the"How to set up a regulating electric valve"Output current calibrationsection to calibrate the output Signal.

2, 신청 조건이 매개변수에 맞는지 확인하시기 바랍니다.

      전동 액추에이터는 부적절한 사용 또는 잘못된 적용 조건으로 인해 고장이 발생할 수 있습니다. 제품 사양에 정의된 사용 조건에서 액추에이터의 장기적인 문제 없는 작동이 보장됩니다.

  • 공급 전압:The voltage of the power supply must be within the rated operating voltage of the actuator. Overvoltage or undervoltage may result in reduced actuator life.
  • Supply current:Since the starting current of the motor is much larger than the rated current. To ensure reliable operation of the actuator, use a power supply with an output current capacity more than three times the rated current of the actuator.
  • Temperature:Ensure that the actuator operates within the rated operating temperature range. Use of the actuator in environments outside of the rated operating temperature range may result in malfunction or reduced service life of the actuator, and ultimately, failure of the actuator.
  • Environment:DCL开关型执行机构具有IP67防风雨等级。一般适用于室内或室外应用。提供一定程度的防雨、防溅水。保护执行器免受雨淋,雪、冰和紫外线(阳光)Typically extends the life of the product. Very corrosive environments may cause premature failure of electronic equipment. Do not use non-explosion-proof series actuators in explosion-proof environments.
  • Energized persistence rate:DCL开关型执行器的通电持续率为70%(每分钟运行42秒,必须关闭18秒),超过70%of the energization duration rate will cause the motor to go into overheat protection.

3、Check that the actuator is wired correctly

E型:带伺服控制器(调节型)

DCL 华易执行器E型接口图

输入:4~20mA / 0~10V Arbitrary Configuration.

输出:4~20mA / 0~10V Arbitrary Configuration.

总线:Modbus / CAN

物联网:WIFI/LoRA/4G DTU

Wiring Instructions:
1、 “电源”输入端的“N”接中线,“L”接 相线;
2、 “输入信号”端的接输入信号的负 极,“+”接输入信号的正极;
3、 “输出信号”端的接直流电流表的 负极,”+”Connect to the positive terminal of the DC ammeter.

 

FType: with position transmitter

DCL 华易执行器F型接口图

通过开关电路实现“开”、“关”operation, and outputs a set of fully open and fully closed active signals.

Wiring Instructions:
1、 “电源”输入端的“N”接中线,“L”接相线;
2、 “电源”输入端的相线“L”接“关”时,向关方向运行,接“开”时,向开方向运行;
3、 “输出信号”端的接直流电流表的负极, “+”Connect to the positive terminal of the DC ammeter.