Application Circuit
Modulieren
E - Modulation mit einer Steuereinheit
- Eingang: 4~20mA / 0~10V
- Ausgang: 4~20 mA / 0~10 V
Connecting Details:
- Connecting AC85-220V supply power line to L and neutral to N.
- Connecting 4-20mA/2-10V input signal source from control system to input-/+.
- Connecting Output -/+ to the system to send out the real-time valve position.
Ein - Aus
A - Mit 2 aktiven Endpositionssignalausgängen
- Steueraktuator zum Öffnen oder Schließen mit K
- Der Ausgangsanschluss der Endposition OPEN/CLOSE sendet das Ereignis als aktives 220VAC-Signal aus, sobald die Endposition erreicht ist.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P5 is end-position OPEN terminal which will output a AC220V source which can be used to drive an Indication light when actuator reached end-position of open.
- P6 is end-position OPEN terminal which will output a AC220V source which can be used to drive an Indication light when actuator reached end-position of close.
- Connect earth to P7.
B - With 2 passive end-position switche
- Steueraktuator zum Öffnen oder Schließen mit K
- Der Ausgangsanschluss der Endposition OPEN/CLOSE sendet das Ereignis als passives Signal aus, sobald die Endposition erreicht ist.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P4 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P5 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P6 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- Connect earth to P7.
G - Gleichstrommotor mit 2 Endschaltern
- Der Stellantrieb wird durch die Richtung der Versorgungsspannung zwischen den Klemmen 1 und 2 zum Öffnen oder Schließen gesteuert.
- Der Ausgangsanschluss der Endposition OPEN/CLOSE sendet das Ereignis als passives Signal aus, sobald die Endposition erreicht ist.
Connecting Details:
- Connecting DC24V+ to P1 and DC24V- to P2 to close the valve.
- Connecting DC24V+ to P2 and DC24V- to P1 to close the valve.
- P3 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P4 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P5 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- Connect earth to P7.