Technical Parameters
| Power Supply | DC24V, AC24V, AC110V, AC220V, AC380V |
| Time/torque | DC24V: 2S/15Nm, 5S/30Nm AC24V/AC110V/AC220V/AC380V: 3S/15Nm, 6S/30Nm |
| control circuit | G-type/A-type/B-type/H-type |
| Rotation Angle | Adjustable from 0 to 270 ° |
| Motor Power/Current | DC24V: 13W/3.0A AC24V: 10W/1.50A AC110V: 10W/0.24A AC220V: 10W/0.16A AC380V: 10W/0.07A |
| Weight | 2.5Kg |
| Insulation Resistance | DC24V: 100MΩ/250VDC AC24V~380V: 100MΩ/500VDC |
| Withstand Voltage | DC/AC24V: 500VAC for 1 minute |
| Water Proof Level | IP67 |
| Installation | 360 ° installation at any angle |
| Electrical Interface | G1/2 waterproof cable joint |
| Working Temperature | -25℃ ~ +55℃ |
| Optional Function | Dehumidification heater, convex indicator |
| Modulation Parameters | |
| Eingangssignal | 4~20mA, 0~10V arbitrary calibration |
| output Signal | 4~20mA, 0~10V arbitrary calibration |
| Bus | 485/Modbus/CAN |
| Internet of Things | WIFI/LoRA/4G |
| Basic Error | ≤±1% |
| Return Error | ≤1% |
| Hysteresis | Adjustable from 0.5% to 5.0% |
| Reposition Times | 0 times |
| Repeatability Error | ≤1% |
Dimensions
Application Circuit
Modulieren
E - Modulation mit einer Steuereinheit
- Eingang: 4~20mA / 0~10V
- Ausgang: 4~20 mA / 0~10 V
- Feldbus: Modbus / CAN
- IIot: WLAN/LoRA/4G DTU
Connecting Details:
- Connecting AC85-220V supply power line to L and neutral to N.
- Connecting 4-20mA/2-10V input signal source from control system to input-/+.
- Connecting Output -/+ to the system to send out the real-time valve position.
Schrittweises Vorgehen und Positionieren
F – Mit einer Positioniereinheit
- Steueraktuator zum Öffnen oder Schließen mit K
- The real-time valve position will be send out as a 4-20mA signal.
Connecting Details:
- Connecting AC85-220V supply power line to L and neutral to N.
- Switch AC85-220V line to CLOSE(P2) to close the valve.
- Switch AC85-220V line to OPEN(P3) to open the valve.
- Connecting Output -/+ to the system to send out the real-time valve position.
C - Mit einem 1 kΩ/500 Ω Potentiometer
- Steueraktuator zum Öffnen oder Schließen mit K
- Die Ventilposition in Echtzeit wird als Widerstandswert des Potentiometers ausgegeben.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P4 is the low side of potentiometer that is normally connected to signal GND.
- Connecting signal input of control system to P5. The resistance value between P4 and P5 will become higher as actuator opening the valve, while the value between P5 and P6 will become lower.
- P6 is the high side of potentiometer that is normally connected to signal power.
- Connect earth to P7.
D – Mit Potentiometer und Endlagenrückmeldung
- Steueraktuator zum Öffnen oder Schließen mit K
- Die Ventilposition in Echtzeit wird als Widerstandswert des Potentiometers ausgegeben.
- Der Ausgangsanschluss der Endposition OPEN/CLOSE sendet das Ereignis als passives Signal aus, sobald die Endposition erreicht ist.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P4 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P5 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P6 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- P7 is the low side of potentiometer that is normally connected to signal GND.
- Connecting signal input of control system to P8. The resistance value between P7 and P8 will become higher as actuator opening the valve, while the value between P8 and P9 will become lower.
- P9 is the high side of potentiometer that is normally connected to signal power.
- Connect earth to P12.
EIN - AUS
A - Mit 2 aktiven Endpositionssignalausgängen
- Steueraktuator zum Öffnen oder Schließen mit K
- Der Ausgangsanschluss der Endposition OPEN/CLOSE sendet das Ereignis als aktives 220VAC-Signal aus, sobald die Endposition erreicht ist.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P5 is end-position OPEN terminal which will output a AC220V source which can be used to drive an Indication light when actuator reached end-position of open.
- P6 is end-position OPEN terminal which will output a AC220V source which can be used to drive an Indication light when actuator reached end-position of close.
- Connect earth to P7.
B – Mit 2 passiven Endpositionsschaltern
- Steueraktuator zum Öffnen oder Schließen mit K
- Der Ausgangsanschluss der Endposition OPEN/CLOSE sendet das Ereignis als passives Signal aus, sobald die Endposition erreicht ist.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P4 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P5 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P6 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- Connect earth to P7.
G - Gleichstrommotor mit 2 Endschaltern
- Der Stellantrieb wird durch die Richtung der Versorgungsspannung zwischen den Klemmen 1 und 2 zum Öffnen oder Schließen gesteuert.
- Der Ausgangsanschluss der Endposition OPEN/CLOSE sendet das Ereignis als passives Signal aus, sobald die Endposition erreicht ist.
Connecting Details:
- Connecting DC24V+ to P1 and DC24V- to P2 to close the valve.
- Connecting DC24V+ to P2 and DC24V- to P1 to close the valve.
- P3 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P4 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P5 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- Connect earth to P7.
H - 3-Phasen-380-V-Wechselstrommotor mit 2 Endschaltern
- Der Stellantrieb wird mittels eines externen Wechselrichters gesteuert, um die Phase der Versorgungsspannung zu ändern und den Stellantrieb zu öffnen oder zu schließen.
- Der Ausgangsanschluss der Endposition OPEN/CLOSE sendet das Ereignis als passives Signal aus, sobald die Endposition erreicht ist.
Connecting Details:
- Connecting a 3 phase AC380V inverter output to P1, P2 and P3, then the actuator can be controlled to open or close the valve by change the 3 phase order.
- Connecting AC380V neutral to N(P4).
- P5 is used for cooperating with an external switch to control the inverter 3 phase order. This terminal is connected to N(P4) when actuator is not in end-position of CLOSE and disconnected from N(P4) after actuator reached end-position of CLOSE.
- P6 is used for cooperating with an external switch to control the inverter 3 phase order. This terminal is connected to N(P4) when actuator is not in end-position of OPEN and disconnected from N(P4) after actuator reached end-position of OPEN.
- P7 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P8 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P9 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- Connect earth to P12.
Notiz:
- Der Schaltkreis im gestrichelten Kasten ist der interne Schaltkreis des Aktuators. Der Schaltkreis außerhalb des Kastens veranschaulicht die elektrische Verbindung zum Betrieb des Aktuators.
- Falls Sie weitere spezielle Anforderungen an die Anschlussschaltung haben, wenden Sie sich bitte an unseren technischen Support.