常見故障排除

Suitable for adjustable actuators

该向导适用于DCLExplosion-Proof/General Series/The adjustable actuators of the quick-opening series are available in the following models:

  • General Series:DCL-05E/DCL-10E/DCL-20E/DCL-40E/DCL-60E/DCL-100E/DCL-160E/DCL-250E
  • Explosion-Proof:DCL-Ex05E/DCL-Ex10E/DCL-Ex20E/DCL-Ex40E/DCL-Ex60E
DCL 華易智控執行器 產品線 | DCL Actuators

1.常見故障及故障排除方法。

過錯可能的原因排除法
在初始啟動期間,致動器不會打開或關閉1.接線不正確根據驅動器的接線圖檢查接線是否正確?
2.電源不正確確認電源供應器的輸出電壓為致動器額定電壓的± 10%,且輸出電流為致動器額定電流的 3 倍。
3. SA is not set to level 1 or 3Check and set SA to either 1st or 3rd gear.
4. Emergency stop switch disconnected (for actuators equipped with emergency stop function)Check and turn on the emergency stop switch.
5. Input Signal exceeds the RangeUse a multimeter to measure the voltage between control modules P3 and P4, and verify if the voltage is within the following Range:
6. Set the fully open and fully closed positions to the same position.參考"How to set up a regulating electric valve 旅行校準section, correctly set the fully open/fully closed position.
The actuator stops before running to the target position1.閥門卡住檢查閥門是否有卡滯現象,消除卡滯現象,並在致動器過載保護冷卻後重試。
2.流體介質中的潛在固體物質可能導致閥門閉鎖。檢查流體介質中是否有固體物體卡住閥門,排除閥門卡住,待執行器過載保護冷卻後重試。
3. Setting the fully open or fully closed position to the middle position is incorrect.參考"How to set up a regulating electric valve 旅行校準section, correctly set the fully open/fully closed position.
4. Incorrect calibration of input signal Range.參考"How to set up a regulating electric valve Input Signal calibrationsection, correctly calibrate the input signal Range.
使用手柄時,致動器無法旋轉流體介質中的潛在固體物質可能導致閥門閉鎖。檢查流體介質中是否有固體物體卡住閥門,排除閥門卡住,待執行器過載保護冷卻後重試。
2.閥門卡住檢查閥門是否有卡滯現象,消除卡滯現象,並在致動器過載保護冷卻後重試。
3.致動器減速機構損壞。將執行器從閥門上取下並轉動手柄。如果無法轉動,請更換新的驅動器。
The feedback signal is incorrect1. Open circuit of the circuitMeasure the voltage between control modules P5 and P6 with a multimeter. If the measured value is>18V, it indicates an open circuit signal. Check and repair any wiring issues.
2. The input impedance of the feedback signal receiving end is too high.Measure and confirm that the input impedance of the feedback signal receiving end is less than 800 ohms
3. Feedback signal calibration error.1. Refer to the"How to set up a regulating electric valve"輸出電流校準section to calibrate the output Signal.

2、請檢查應用條件是否與參數相符。

      由於使用不當或在錯誤的應用條件下,電動推桿可能會發生故障。在產品規格中定義的應用條件下,可確保執行器的長期無故障運行。

  • 供應電壓:電源的電壓必須在執行機構的額定工作電壓之內。電壓過高或過低都可能導致驅動器壽命縮短。
  • 供應電流:由於馬達的啟動電流遠大於額定電流,為確保執行器可靠運行,因此應使用輸出電流容量大於執行器額定電流三倍的電源。
  • 溫度:确保执行机构在额定工作温度范围内运行。在超出額定工作溫度範圍的環境中使用致動器,可能會導致致動器故障或使用壽命縮短,最終導致致動器失效。
  • 環境:DCL开关型执行机构具有IP67防风雨等级。一般适用于室内或室外应用。提供一定程度的防雨、防溅水。保护执行器免受雨淋、雪、冰和紫外线(阳光)腐蚀,基本上延长了产品的使用寿命。腐蝕性極高的環境可能導致電子設備過早故障。請勿在防爆環境中使用非防爆系列執行器。
  • 活力持久率:DCL開關型執行器的通電持續率為70%(每分鐘運行42秒,必須關閉18秒),超過70%的通電持續率會使馬達進入過熱保護狀態。

3、檢查執行器接線是否正確

E型:附服務員控制器(調節型)

DCL 華易執行器E型介面圖

輸入:4~20mA / 0~10V 任意配置。

輸出:4~20mA / 0~10V 任意配置。

介面:Modbus / CAN

物聯網:WIFI/LoRA/4G DTU

接線指示:
1.「電源」輸入端的「N」接中線,「L」接相線;
2.「輸入訊號」端接輸入訊號的負極,「+」接輸入訊號的接腳;
3.「輸出訊號」端接直流電表的電壓,「+」接直流電流表的正極端子。

 

FType: with position transmitter

DCL 华易执行器F型接口图

通過開關電路實現 「開」、「關 」操作,並輸出一組全開和全關的有源信號。

接線指示:
1、 “电源”输入端的“N”接中线,“L”接相线;
2、 “电源”输入端的相线“L”接“关”时,向关方向运行,接“开”时,向开方向运行;
3、 “输出信号”端的接直流电流表的负极, “+”Connect to the positive terminal of the DC ammeter.