常見故障排除
Suitable for adjustable actuators
该向导适用于DCLExplosion-Proof/General Series/The adjustable actuators of the quick-opening series are available in the following models:
- General Series:DCL-05E/DCL-10E/DCL-20E/DCL-40E/DCL-60E/DCL-100E/DCL-160E/DCL-250E
- Explosion-Proof:DCL-Ex05E/DCL-Ex10E/DCL-Ex20E/DCL-Ex40E/DCL-Ex60E
1.常見故障及故障排除方法。
| 過錯 | 可能的原因 | 排除法 |
|---|---|---|
| 在初始啟動期間,致動器不會打開或關閉 | 1.接線不正確 | 根據驅動器的接線圖檢查接線是否正確? |
| 2.電源不正確 | 確認電源供應器的輸出電壓為致動器額定電壓的± 10%,且輸出電流為致動器額定電流的 3 倍。 | |
| 3. SA is not set to level 1 or 3 | Check and set SA to either 1st or 3rd gear. | |
| 4. Emergency stop switch disconnected (for actuators equipped with emergency stop function) | Check and turn on the emergency stop switch. | |
| 5. Input Signal exceeds the Range | Use a multimeter to measure the voltage between control modules P3 and P4, and verify if the voltage is within the following Range: | |
| 6. Set the fully open and fully closed positions to the same position. | 參考"How to set up a regulating electric valve 旅行校準section, correctly set the fully open/fully closed position. | |
| The actuator stops before running to the target position | 1.閥門卡住 | 檢查閥門是否有卡滯現象,消除卡滯現象,並在致動器過載保護冷卻後重試。 |
| 2.流體介質中的潛在固體物質可能導致閥門閉鎖。 | 檢查流體介質中是否有固體物體卡住閥門,排除閥門卡住,待執行器過載保護冷卻後重試。 | |
| 3. Setting the fully open or fully closed position to the middle position is incorrect. | 參考"How to set up a regulating electric valve 旅行校準section, correctly set the fully open/fully closed position. | |
| 4. Incorrect calibration of input signal Range. | 參考"How to set up a regulating electric valve Input Signal calibrationsection, correctly calibrate the input signal Range. | |
| 使用手柄時,致動器無法旋轉 | 流體介質中的潛在固體物質可能導致閥門閉鎖。 | 檢查流體介質中是否有固體物體卡住閥門,排除閥門卡住,待執行器過載保護冷卻後重試。 |
| 2.閥門卡住 | 檢查閥門是否有卡滯現象,消除卡滯現象,並在致動器過載保護冷卻後重試。 | |
| 3.致動器減速機構損壞。 | 將執行器從閥門上取下並轉動手柄。如果無法轉動,請更換新的驅動器。 | |
| The feedback signal is incorrect | 1. Open circuit of the circuit | Measure the voltage between control modules P5 and P6 with a multimeter. If the measured value is>18V, it indicates an open circuit signal. Check and repair any wiring issues. |
| 2. The input impedance of the feedback signal receiving end is too high. | Measure and confirm that the input impedance of the feedback signal receiving end is less than 800 ohms | |
| 3. Feedback signal calibration error. | 1. Refer to the"How to set up a regulating electric valve"輸出電流校準section to calibrate the output Signal. |
2、請檢查應用條件是否與參數相符。
由於使用不當或在錯誤的應用條件下,電動推桿可能會發生故障。在產品規格中定義的應用條件下,可確保執行器的長期無故障運行。
- 供應電壓:電源的電壓必須在執行機構的額定工作電壓之內。電壓過高或過低都可能導致驅動器壽命縮短。
- 供應電流:由於馬達的啟動電流遠大於額定電流,為確保執行器可靠運行,因此應使用輸出電流容量大於執行器額定電流三倍的電源。
- 溫度:确保执行机构在额定工作温度范围内运行。在超出額定工作溫度範圍的環境中使用致動器,可能會導致致動器故障或使用壽命縮短,最終導致致動器失效。
- 環境:DCL开关型执行机构具有IP67防风雨等级。一般适用于室内或室外应用。提供一定程度的防雨、防溅水。保护执行器免受雨淋、雪、冰和紫外线(阳光)腐蚀,基本上延长了产品的使用寿命。腐蝕性極高的環境可能導致電子設備過早故障。請勿在防爆環境中使用非防爆系列執行器。
- 活力持久率:DCL開關型執行器的通電持續率為70%(每分鐘運行42秒,必須關閉18秒),超過70%的通電持續率會使馬達進入過熱保護狀態。
3、檢查執行器接線是否正確
E型:附服務員控制器(調節型)
輸入:4~20mA / 0~10V 任意配置。
輸出:4~20mA / 0~10V 任意配置。
介面:Modbus / CAN
物聯網:WIFI/LoRA/4G DTU
接線指示:
1.「電源」輸入端的「N」接中線,「L」接相線;
2.「輸入訊號」端接輸入訊號的負極,「+」接輸入訊號的接腳;
3.「輸出訊號」端接直流電表的電壓,「+」接直流電流表的正極端子。
FType: with position transmitter
通過開關電路實現 「開」、「關 」操作,並輸出一組全開和全關的有源信號。
接線指示:
1、 “电源”输入端的“N”接中线,“L”接相线;
2、 “电源”输入端的相线“L”接“关”时,向关方向运行,接“开”时,向开方向运行;
3、 “输出信号”端的接直流电流表的负极, “+”Connect to the positive terminal of the DC ammeter.