{"id":6033,"date":"2023-08-03T20:44:54","date_gmt":"2023-08-03T12:44:54","guid":{"rendered":"https:\/\/www.dcl-controls.com\/?p=6033"},"modified":"2025-03-27T09:47:56","modified_gmt":"2025-03-27T09:47:56","slug":"dcl-02-on-off-actuator","status":"publish","type":"post","link":"https:\/\/dclcontrols.com\/es_mx\/apoyo\/sr-actuador\/actuador-de-encendido-apagado-dcl-02","title":{"rendered":"Fallos comunes y soluci\u00f3n de problemas para los actuadores de encendido\/apagado DCL-02"},"content":{"rendered":"<div data-elementor-type=\"wp-post\" data-elementor-id=\"6033\" class=\"elementor elementor-6033\" data-elementor-post-type=\"post\">\n\t\t\t\t<div class=\"elementor-element elementor-element-23bbd22 e-con-full e-flex e-con e-parent\" data-id=\"23bbd22\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t<div class=\"elementor-element elementor-element-add184b e-con-full e-flex e-con e-child\" data-id=\"add184b\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t<div class=\"elementor-element elementor-element-ec8fa0c elementor-widget elementor-widget-text-editor\" data-id=\"ec8fa0c\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"\" data-start=\"0\" data-end=\"92\">Esta gu\u00eda es aplicable a los actuadores de la serie DCL Ultra-Small, con los siguientes modelos:<\/p><ul data-start=\"94\" data-end=\"123\"><li class=\"\" data-start=\"94\" data-end=\"103\"><p class=\"\" data-start=\"96\" data-end=\"103\">DCL-02A<\/p><\/li><li class=\"\" data-start=\"104\" data-end=\"113\"><p class=\"\" data-start=\"106\" data-end=\"113\">DCL-02B<\/p><\/li><li class=\"\" data-start=\"114\" data-end=\"123\"><p class=\"\" data-start=\"116\" data-end=\"123\">DCL-02G<\/p><\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-69c14e5 elementor-widget elementor-widget-image\" data-id=\"69c14e5\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img fetchpriority=\"high\" decoding=\"async\" width=\"176\" height=\"399\" src=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2023\/05\/dcl-02-valve.webp\" class=\"attachment-full size-full wp-image-4861\" alt=\"\u534e\u6613\u7cbe\u5de7\u7cfb\u5217\u6267\u884c\u5668 DCL-02 Accesorios | V\u00e1lvula actuadora DCL-02\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-b43d346 elementor-widget elementor-widget-heading\" data-id=\"b43d346\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<h2 class=\"elementor-heading-title elementor-size-default\">Fallos comunes y m\u00e9todos de soluci\u00f3n de problemas<\/h2>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-e1d44fb elementor-widget elementor-widget-text-editor\" data-id=\"e1d44fb\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p>\u00a0<\/p><table><thead><tr><th><strong>Falla<\/strong><\/th><th><strong>Posibles causas<\/strong><\/th><th><strong>M\u00e9todos de soluci\u00f3n de problemas<\/strong><\/th><\/tr><\/thead><tbody><tr><td><strong>El actuador no se abre ni se cierra al arrancar inicialmente.<\/strong><\/td><td>1. Cableado incorrecto<\/td><td>Verifique el cableado seg\u00fan el diagrama de cableado del actuador.<\/td><\/tr><tr><td>\u00a0<\/td><td>2. Fuente de alimentaci\u00f3n incorrecta<\/td><td>Aseg\u00farese de que la tensi\u00f3n de la fuente de alimentaci\u00f3n est\u00e9 dentro de \u00b110% de la tensi\u00f3n nominal del actuador y que la corriente sea 3 veces la corriente nominal.<\/td><\/tr><tr><td>\u00a0<\/td><td>3. Interruptor o rel\u00e9 de control defectuoso.<\/td><td>Mida la tensi\u00f3n de entrada en el terminal de control del actuador utilizando un mult\u00edmetro para verificar que coincida con lo esperado.<\/td><\/tr><tr><td>\u00a0<\/td><td>4. Desajuste del sistema de control<\/td><td>Pruebe el actuador con un interruptor mec\u00e1nico. Si funciona correctamente, verifique la l\u00f3gica de salida del sistema de control.<\/td><\/tr><tr><td>\u00a0<\/td><td>5. M\u00faltiples actuadores o actuadores y otros dispositivos conectados en paralelo<\/td><td>Los actuadores de interruptor deben utilizar control de v\u00eda \u00fanica y no conectarse en paralelo, ya que esto afecta al condensador de arranque.<\/td><\/tr><tr><td><strong>El actuador solo puede abrir o cerrar.<\/strong><\/td><td>1. Cableado incorrecto<\/td><td>Compruebe el cableado utilizando el diagrama de cableado del actuador.<\/td><\/tr><tr><td>\u00a0<\/td><td>2. Ajuste incorrecto de apertura\/cierre total de la leva.<\/td><td>Consulte la gu\u00eda &quot;C\u00f3mo ajustar las v\u00e1lvulas de interruptor el\u00e9ctrico&quot; y ajuste correctamente las posiciones de la leva.<\/td><\/tr><tr><td><strong>El actuador se detiene a mitad del recorrido.<\/strong><\/td><td>1. V\u00e1lvula atascada<\/td><td>Compruebe si hay obstrucciones en la v\u00e1lvula. Elimine cualquier obstrucci\u00f3n y vuelva a intentarlo despu\u00e9s de que se enfr\u00ede la protecci\u00f3n contra sobrecarga del actuador.<\/td><\/tr><tr><td>\u00a0<\/td><td>2. Material s\u00f3lido en el fluido que provoca atasco de la v\u00e1lvula<\/td><td>Inspeccione el fluido para detectar part\u00edculas s\u00f3lidas que puedan estar causando atascos en las v\u00e1lvulas. Elimine el atasco y vuelva a intentarlo una vez que se enfr\u00ede la protecci\u00f3n contra sobrecarga del actuador.<\/td><\/tr><tr><td>\u00a0<\/td><td>3. Ajuste incorrecto del tope de apertura\/cierre total.<\/td><td>Consulte la gu\u00eda &quot;C\u00f3mo ajustar las v\u00e1lvulas el\u00e9ctricas de tipo interruptor&quot; y ajuste correctamente la posici\u00f3n de los topes.<\/td><\/tr><tr><td><strong>No es posible girar el actuador usando la manivela.<\/strong><\/td><td>1. Presencia de material s\u00f3lido en el fluido que provoca el bloqueo de la v\u00e1lvula.<\/td><td>Compruebe si hay alguna obstrucci\u00f3n en la v\u00e1lvula. Elimine la obstrucci\u00f3n y vuelva a intentarlo una vez que se enfr\u00ede la protecci\u00f3n contra sobrecarga del actuador.<\/td><\/tr><tr><td>\u00a0<\/td><td>2. Atascamiento de la v\u00e1lvula<\/td><td>Inspeccione la v\u00e1lvula para detectar posibles atascos. Elimine la obstrucci\u00f3n y vuelva a intentarlo una vez que se haya enfriado la protecci\u00f3n contra sobrecarga del actuador.<\/td><\/tr><tr><td>\u00a0<\/td><td>3. Mecanismo de reducci\u00f3n del actuador da\u00f1ado<\/td><td>Retire el actuador de la v\u00e1lvula y gire la manija. Si no se mueve, reemplace el actuador.<\/td><\/tr><tr><td><strong>Sin se\u00f1al de retroalimentaci\u00f3n de posici\u00f3n<\/strong><\/td><td>1. Cableado incorrecto en el interruptor.<\/td><td>Verifique el cableado seg\u00fan el diagrama de cableado del actuador.<\/td><\/tr><tr><td>\u00a0<\/td><td>2. Ajuste incorrecto de apertura\/cierre total de la leva.<\/td><td>Consulte la gu\u00eda &quot;C\u00f3mo ajustar las v\u00e1lvulas de interruptor el\u00e9ctrico&quot; y ajuste correctamente la posici\u00f3n de la leva.<\/td><\/tr><tr><td>\u00a0<\/td><td>3. Sobrecorriente que provoca da\u00f1os en el interruptor de retroalimentaci\u00f3n de posici\u00f3n.<\/td><td>1. Compruebe si la leva de apertura\/cierre total est\u00e1 presionando correctamente el interruptor de retroalimentaci\u00f3n de posici\u00f3n, seg\u00fan la gu\u00eda.<\/td><\/tr><tr><td>\u00a0<\/td><td>\u00a0<\/td><td>2. Mida si el circuito de retroalimentaci\u00f3n de posici\u00f3n est\u00e1 cerrado.<\/td><\/tr><\/tbody><\/table><p>\u00a0<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-d58177d elementor-widget elementor-widget-heading\" data-id=\"d58177d\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<h2 class=\"elementor-heading-title elementor-size-default\">Verifique que las condiciones de funcionamiento cumplan con los requisitos de los par\u00e1metros.<\/h2>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-60cdda7 elementor-widget elementor-widget-text-editor\" data-id=\"60cdda7\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"\" data-start=\"156\" data-end=\"422\">Los actuadores el\u00e9ctricos pueden fallar debido a un uso inadecuado o a su uso en condiciones de funcionamiento incorrectas. Cuando se utilizan dentro de las condiciones de funcionamiento definidas en las especificaciones del producto, se espera que el actuador funcione de manera confiable durante un per\u00edodo prolongado sin fallar.<\/p><ul data-start=\"424\" data-end=\"1721\"><li class=\"\" data-start=\"424\" data-end=\"610\"><p class=\"\" data-start=\"426\" data-end=\"610\"><strong data-start=\"426\" data-end=\"445\">Tensi\u00f3n de alimentaci\u00f3n:<\/strong> La tensi\u00f3n de la fuente de alimentaci\u00f3n debe estar dentro del rango de tensi\u00f3n de funcionamiento nominal del actuador. Una sobretensi\u00f3n o una subtensi\u00f3n pueden acortar la vida \u00fatil del actuador.<\/p><\/li><li class=\"\" data-start=\"614\" data-end=\"840\"><p class=\"\" data-start=\"616\" data-end=\"840\"><strong data-start=\"616\" data-end=\"635\">Corriente de suministro:<\/strong> La corriente de arranque del motor es significativamente superior a la corriente nominal. Para garantizar un funcionamiento fiable, utilice una fuente de alimentaci\u00f3n capaz de suministrar al menos tres veces la corriente nominal del actuador.<\/p><\/li><li class=\"\" data-start=\"842\" data-end=\"1035\"><p class=\"\" data-start=\"844\" data-end=\"1035\"><strong data-start=\"844\" data-end=\"860\">Temperatura:<\/strong> Aseg\u00farese de que el actuador funcione dentro de su rango de temperatura nominal. Utilizarlo fuera de este rango puede provocar un rendimiento deficiente, una menor vida \u00fatil y, finalmente, su fallo.<\/p><\/li><li class=\"\" data-start=\"1037\" data-end=\"1504\"><p class=\"\" data-start=\"1039\" data-end=\"1504\"><strong data-start=\"1039\" data-end=\"1055\">Ambiente:<\/strong> El actuador de tipo interruptor DCL cuenta con una clasificaci\u00f3n de protecci\u00f3n IP67 contra la intemperie, lo que lo hace apto para aplicaciones tanto en interiores como en exteriores. Ofrece protecci\u00f3n contra la lluvia y las salpicaduras de agua, prolongando su vida \u00fatil al protegerlo de la lluvia, la nieve, el hielo y la radiaci\u00f3n UV (luz solar). Sin embargo, en entornos altamente corrosivos, los componentes electr\u00f3nicos pueden fallar prematuramente. Los actuadores no antiexplosivos no deben utilizarse en entornos explosivos.<\/p><\/li><li class=\"\" data-start=\"1506\" data-end=\"1721\"><p class=\"\" data-start=\"1508\" data-end=\"1721\"><strong data-start=\"1508\" data-end=\"1523\">Ciclo de trabajo:<\/strong> El actuador de tipo interruptor DCL tiene un ciclo de trabajo de 70% (42 segundos de funcionamiento por minuto, seguidos de 18 segundos de reposo). Si se supera este ciclo de trabajo, el motor podr\u00eda activar la protecci\u00f3n t\u00e9rmica.<\/p><\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-0273976 elementor-widget elementor-widget-heading\" data-id=\"0273976\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<h2 class=\"elementor-heading-title elementor-size-default\">Compruebe el cableado del actuador.<\/h2>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-9df2216 elementor-widget elementor-widget-text-editor\" data-id=\"9df2216\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"\" data-start=\"45\" data-end=\"186\">Aseg\u00farese de que el actuador est\u00e9 cableado correctamente seg\u00fan el diagrama de cableado proporcionado por el fabricante. Siga estos pasos para verificar el cableado:<\/p><ol data-start=\"188\" data-end=\"1007\"><li class=\"\" data-start=\"188\" data-end=\"325\"><p class=\"\" data-start=\"191\" data-end=\"209\"><strong data-start=\"191\" data-end=\"208\">Fuente de alimentaci\u00f3n:<\/strong><\/p><ul data-start=\"213\" data-end=\"325\"><li class=\"\" data-start=\"213\" data-end=\"321\"><p class=\"\" data-start=\"215\" data-end=\"321\">Compruebe las conexiones de la fuente de alimentaci\u00f3n para asegurarse de que coinciden con la tensi\u00f3n y la corriente de entrada requeridas por el actuador.<\/p><\/li><\/ul><\/li><li class=\"\" data-start=\"326\" data-end=\"504\"><p class=\"\" data-start=\"329\" data-end=\"353\"><strong data-start=\"329\" data-end=\"353\">Conexiones de control:<\/strong><\/p><ul data-start=\"357\" data-end=\"504\"><li class=\"\" data-start=\"357\" data-end=\"504\"><p class=\"\" data-start=\"359\" data-end=\"504\">Verifique que las conexiones de control de entrada y salida est\u00e9n bien sujetas y configuradas correctamente seg\u00fan el diagrama de cableado del actuador.<\/p><\/li><\/ul><\/li><li class=\"\" data-start=\"506\" data-end=\"707\"><p class=\"\" data-start=\"509\" data-end=\"527\"><strong data-start=\"509\" data-end=\"527\">Cableado de se\u00f1al:<\/strong><\/p><ul data-start=\"531\" data-end=\"707\"><li class=\"\" data-start=\"531\" data-end=\"639\"><p class=\"\" data-start=\"533\" data-end=\"639\">Compruebe el cableado para detectar se\u00f1ales de control, como 4-20 mA o 0-10 V, seg\u00fan las especificaciones del actuador.<\/p><\/li><li class=\"\" data-start=\"643\" data-end=\"707\"><p class=\"\" data-start=\"645\" data-end=\"707\">Compruebe que no haya conexiones sueltas ni cortocircuitos.<\/p><\/li><\/ul><\/li><li class=\"\" data-start=\"709\" data-end=\"823\"><p class=\"\" data-start=\"712\" data-end=\"726\"><strong data-start=\"712\" data-end=\"726\">Toma de tierra:<\/strong><\/p><ul data-start=\"730\" data-end=\"823\"><li class=\"\" data-start=\"730\" data-end=\"823\"><p class=\"\" data-start=\"732\" data-end=\"823\">Aseg\u00farese de que el actuador est\u00e9 correctamente conectado a tierra para evitar interferencias el\u00e9ctricas o da\u00f1os.<\/p><\/li><\/ul><\/li><li class=\"\" data-start=\"825\" data-end=\"1007\"><p class=\"\" data-start=\"828\" data-end=\"863\"><strong data-start=\"828\" data-end=\"863\">Conexiones a otros equipos:<\/strong><\/p><ul data-start=\"867\" data-end=\"1007\"><li class=\"\" data-start=\"867\" data-end=\"1007\"><p class=\"\" data-start=\"869\" data-end=\"1007\">Si el actuador est\u00e1 conectado a otros dispositivos, aseg\u00farese de que esas conexiones tambi\u00e9n sean correctas y no causen interferencias ni problemas de alimentaci\u00f3n el\u00e9ctrica.<\/p><\/li><\/ul><\/li><\/ol><p class=\"\" data-start=\"1009\" data-end=\"1155\">Si el cableado parece correcto, pero el actuador sigue funcionando mal, puede ser necesario realizar m\u00e1s comprobaciones o solicitar la ayuda de un t\u00e9cnico.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t<div class=\"elementor-element elementor-element-84857ae e-flex e-con-boxed e-con e-parent\" data-id=\"84857ae\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t\t<div class=\"e-con-inner\">\n\t\t\t\t<div class=\"elementor-element elementor-element-cf23cb0 elementor-widget elementor-widget-template\" data-id=\"cf23cb0\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"template.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t<div class=\"elementor-template\">\n\t\t\t\t\t<div data-elementor-type=\"section\" data-elementor-id=\"10969\" class=\"elementor elementor-10969\" data-elementor-post-type=\"elementor_library\">\n\t\t\t<div class=\"elementor-element elementor-element-d642a8e e-flex e-con-boxed e-con e-parent\" data-id=\"d642a8e\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t\t<div class=\"e-con-inner\">\n\t\t<div class=\"elementor-element elementor-element-4dcc388 e-con-full e-flex e-con e-child\" data-id=\"4dcc388\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t<div class=\"elementor-element elementor-element-09f4232 elementor-widget elementor-widget-heading\" data-id=\"09f4232\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<p class=\"elementor-heading-title elementor-size-default\">A - Con 2 salidas de se\u00f1al de posici\u00f3n final activas<\/p>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-daf3293 elementor-widget elementor-widget-image\" data-id=\"daf3293\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img decoding=\"async\" width=\"400\" height=\"341\" src=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2023\/05\/dcl-actuator-interface-diagram-a.webp\" class=\"attachment-full size-full wp-image-4860\" alt=\"DCL \u534e\u6613\u6267\u884c\u5668A\u578b\u63a5\u53e3\u56fe\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-14e5438 elementor-widget elementor-widget-text-editor\" data-id=\"14e5438\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<ul><li>Controlar el actuador para abrir o cerrar con K<\/li><li>El terminal de salida de la posici\u00f3n final APERTURA\/CIERRE enviar\u00e1 el evento como una se\u00f1al activa de 220 VCA cuando se alcance la posici\u00f3n final.<\/li><\/ul><p>\u00a0<\/p><p><strong>Detalles de conexi\u00f3n:<\/strong><\/p><ol><li>Conectar el neutro de la fuente de alimentaci\u00f3n de CA 85-220 V a P1.<\/li><li>Cambie la l\u00ednea AC85-220V a la posici\u00f3n CERRAR (P2) para cerrar la v\u00e1lvula.<\/li><li>Para abrir la v\u00e1lvula, coloque el interruptor de la l\u00ednea AC85-220V en la posici\u00f3n ABIERTA (P3).<\/li><li>P5 es el terminal de posici\u00f3n final ABIERTA que proporciona una fuente de CA de 220 V que se puede utilizar para encender una luz indicadora cuando el actuador alcanza la posici\u00f3n final de apertura.<\/li><li>P6 es el terminal de posici\u00f3n final ABIERTO que proporciona una fuente de CA de 220 V que se puede utilizar para encender una luz indicadora cuando el actuador alcanza la posici\u00f3n final de cierre.<\/li><li>Conecte la toma de tierra a P7.<\/li><\/ol>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t<div class=\"elementor-element elementor-element-f1a67a7 e-con-full e-flex e-con e-child\" data-id=\"f1a67a7\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t<div class=\"elementor-element elementor-element-a942089 elementor-widget elementor-widget-heading\" data-id=\"a942089\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<p class=\"elementor-heading-title elementor-size-default\">B - Con 2 interruptores pasivos de posici\u00f3n final<\/p>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-766f845 elementor-widget elementor-widget-image\" data-id=\"766f845\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img decoding=\"async\" width=\"400\" height=\"348\" src=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2023\/05\/dcl-actuator-interface-diagram-b.webp\" class=\"attachment-full size-full wp-image-4858\" alt=\"DCL \u534e\u6613\u6267\u884c\u5668B\u578b\u63a5\u53e3\u56fe\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-799d994 elementor-widget elementor-widget-text-editor\" data-id=\"799d994\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<ul><li>Controlar el actuador para abrir o cerrar con K<\/li><li>El terminal de salida de la posici\u00f3n final APERTURA\/CIERRE enviar\u00e1 el evento como una se\u00f1al pasiva cuando se alcance la posici\u00f3n final.<\/li><\/ul><p>\u00a0<\/p><p><strong>Detalles de conexi\u00f3n:<\/strong><\/p><ol><li>Conectar el neutro de la fuente de alimentaci\u00f3n de CA 85-220 V a P1.<\/li><li>Cambie la l\u00ednea AC85-220V a la posici\u00f3n CERRAR (P2) para cerrar la v\u00e1lvula.<\/li><li>Para abrir la v\u00e1lvula, coloque el interruptor de la l\u00ednea AC85-220V en la posici\u00f3n ABIERTA (P3).<\/li><li>P4 es el COM para la se\u00f1al de contacto pasivo de posici\u00f3n final ABIERTA\/CERRADA que normalmente est\u00e1 conectada a la se\u00f1al GND.<\/li><li>P5 es el terminal de posici\u00f3n final ABIERTA que se conectar\u00e1 a COM cuando el actuador alcance la posici\u00f3n final de apertura.<\/li><li>P6 es el terminal de cierre de posici\u00f3n final que se conectar\u00e1 a COM cuando el actuador alcance la posici\u00f3n final de cierre.<\/li><li>Conecte la toma de tierra a P7.<\/li><\/ol>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t<div class=\"elementor-element elementor-element-738bf4f e-con-full e-flex e-con e-child\" data-id=\"738bf4f\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t<div class=\"elementor-element elementor-element-5a73aaa elementor-widget elementor-widget-heading\" data-id=\"5a73aaa\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<p class=\"elementor-heading-title elementor-size-default\">G - Motor de CC con 2 interruptores de posici\u00f3n final.<\/p>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-8c393f4 elementor-widget elementor-widget-image\" data-id=\"8c393f4\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img loading=\"lazy\" decoding=\"async\" width=\"400\" height=\"391\" src=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2023\/05\/dcl-actuator-interface-diagram-g.webp\" class=\"attachment-full size-full wp-image-4853\" alt=\"DCL \u534e\u6613\u6267\u884c\u5668G\u578b\u63a5\u53e3\u56fe\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-a35d4cf elementor-widget elementor-widget-text-editor\" data-id=\"a35d4cf\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<ul><li>Controla el actuador para que se abra o se cierre mediante la direcci\u00f3n de la alimentaci\u00f3n el\u00e9ctrica entre los terminales 1 y 2.<\/li><li>El terminal de salida de la posici\u00f3n final APERTURA\/CIERRE enviar\u00e1 el evento como una se\u00f1al pasiva cuando se alcance la posici\u00f3n final.<\/li><\/ul><p>\u00a0<\/p><p><strong>Detalles de conexi\u00f3n:<\/strong><\/p><ol><li>Conecte DC24V+ a P1 y DC24V- a P2 para cerrar la v\u00e1lvula.<\/li><li>Conecte DC24V+ a P2 y DC24V- a P1 para cerrar la v\u00e1lvula.<\/li><li>P3 es el COM para la se\u00f1al de contacto pasivo de posici\u00f3n final ABIERTA\/CERRADA que normalmente est\u00e1 conectada a la se\u00f1al GND.<\/li><li>P4 es el terminal de posici\u00f3n final ABIERTA que se conectar\u00e1 a COM cuando el actuador alcance la posici\u00f3n final de apertura.<\/li><li>P5 es el terminal de cierre de posici\u00f3n final que se conectar\u00e1 a COM cuando el actuador alcance la posici\u00f3n final de cierre.<\/li><li>Conecte la toma de tierra a P7.<\/li><\/ol>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t<div class=\"elementor-element elementor-element-ff65758 e-con-full e-flex e-con e-parent\" data-id=\"ff65758\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t<div class=\"elementor-element elementor-element-d5dc048 e-con-full e-flex e-con e-child\" data-id=\"d5dc048\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t<div class=\"elementor-element elementor-element-527200f elementor-widget elementor-widget-text-editor\" data-id=\"527200f\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p>Nota:<\/p><ul><li>El circuito dentro del recuadro punteado es el circuito interno del actuador. El circuito exterior muestra la conexi\u00f3n el\u00e9ctrica para el funcionamiento del actuador.<\/li><li>Si tiene otros requisitos espec\u00edficos sobre la conexi\u00f3n del circuito, no dude en ponerse en contacto con nuestro servicio de asistencia t\u00e9cnica.\u00a0<\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-002d845 elementor-widget elementor-widget-text-editor\" data-id=\"002d845\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p>Cuando realice tareas de resoluci\u00f3n de problemas in situ, no dude en ponerse en contacto con nuestro personal de servicio t\u00e9cnico de inmediato para obtener ayuda en el diagn\u00f3stico y la soluci\u00f3n del problema. <br \/>N\u00famero de tel\u00e9fono de contacto: 13026331611 (Sr. Chen)<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>","protected":false},"excerpt":{"rendered":"<p>Esta gu\u00eda es aplicable a los actuadores de la serie DCL Ultra-Small, con los siguientes modelos: DCL-02A, DCL-02B y DCL-02G. Fallas comunes y m\u00e9todos de soluci\u00f3n de problemas. Falla Posibles causas M\u00e9todos de soluci\u00f3n de problemas El actuador no se abre ni se cierra al arrancar inicialmente. 1. Cableado incorrecto. Compruebe el cableado seg\u00fan el diagrama de cableado del actuador. 2. Alimentaci\u00f3n el\u00e9ctrica incorrecta. Aseg\u00farese de que [\u2026]<\/p>","protected":false},"author":1,"featured_media":0,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"elementor_theme","format":"standard","meta":{"_acf_changed":true,"footnotes":""},"categories":[103],"tags":[53],"class_list":["post-6033","post","type-post","status-publish","format-standard","hentry","category-mr-actuator","tag-actuator"],"acf":[],"_links":{"self":[{"href":"https:\/\/dclcontrols.com\/es_mx\/wp-json\/wp\/v2\/posts\/6033","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/dclcontrols.com\/es_mx\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/dclcontrols.com\/es_mx\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/dclcontrols.com\/es_mx\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/dclcontrols.com\/es_mx\/wp-json\/wp\/v2\/comments?post=6033"}],"version-history":[{"count":0,"href":"https:\/\/dclcontrols.com\/es_mx\/wp-json\/wp\/v2\/posts\/6033\/revisions"}],"wp:attachment":[{"href":"https:\/\/dclcontrols.com\/es_mx\/wp-json\/wp\/v2\/media?parent=6033"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/dclcontrols.com\/es_mx\/wp-json\/wp\/v2\/categories?post=6033"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/dclcontrols.com\/es_mx\/wp-json\/wp\/v2\/tags?post=6033"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}