{"id":6032,"date":"2023-08-03T20:13:29","date_gmt":"2023-08-03T12:13:29","guid":{"rendered":"https:\/\/www.dcl-controls.com\/?p=6032"},"modified":"2025-03-27T08:36:44","modified_gmt":"2025-03-27T08:36:44","slug":"on-off-actuator","status":"publish","type":"post","link":"https:\/\/dclcontrols.com\/es_cl\/apoyo\/mr-actuator\/on-off-actuator","title":{"rendered":"Common faults &amp; troubleshooting for ON-OFF actuators"},"content":{"rendered":"<div data-elementor-type=\"wp-post\" data-elementor-id=\"6032\" class=\"elementor elementor-6032\" data-elementor-post-type=\"post\">\n\t\t\t\t<div class=\"elementor-element elementor-element-c46c850 e-con-full e-flex e-con e-child\" data-id=\"c46c850\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t<div class=\"elementor-element elementor-element-bbe1880 elementor-widget elementor-widget-text-editor\" data-id=\"bbe1880\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p>This guide applies to the switch-type actuators of the DCL explosion-proof series, standard series, and quick-open series. The models are as follows:<\/p><p><strong>Weather-proof Actuator:<\/strong> DCL-05, DCL-10, DCL-20, DCL-40, DCL-60, DCL-100, DCL-160, DCL-250<br \/><strong>Explosion-Proof Actuator:<\/strong> DCL-Ex05, DCL-Ex10, DCL-Ex20, DCL-Ex40, DCL-Ex60<br \/><strong>Quick-Turn Actuator:<\/strong> DCL-K05, DCL-K10, DCL-K20, DCL-K40, DCL-K100<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-3e76288 elementor-widget elementor-widget-heading\" data-id=\"3e76288\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<h1 class=\"elementor-heading-title elementor-size-default\">Common Faults and Troubleshooting Methods<\/h1>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-f9da4e2 elementor-widget elementor-widget-text-editor\" data-id=\"f9da4e2\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p>\u00a0<\/p><table><thead><tr><th><strong>Fault<\/strong><\/th><th><strong>Possible Causes<\/strong><\/th><th><strong>Troubleshooting Methods<\/strong><\/th><\/tr><\/thead><tbody><tr><td><strong>Actuator does not open or close at startup<\/strong><\/td><td><p>1. Incorrect wiring.<\/p><p>2. Incorrect power supply.<\/p><p>3. Faulty control switch or relay.<\/p><p>4. Control system mismatch.<\/p><p>5. Multiple actuators or actuator in parallel with other devices.<\/p><\/td><td><p>1. Check the wiring against the actuator\u2019s wiring diagram to ensure it is correct.<\/p><p>2. Verify power supply output voltage is \u00b110% of rated voltage, and the current is at least three times the actuator\u2019s rated current.<\/p><p>3. Use a multimeter to measure input voltage at the actuator&#8217;s control terminal and confirm it matches expected values.<\/p><p>4. Use a mechanical switch to test actuator operation. If it works, verify the control system output logic.<\/p><p>5. Switch-type actuators should not be connected in parallel with other devices; use a single control circuit.<\/p><\/td><\/tr><tr><td><strong>Actuator only opens or closes, not both<\/strong><\/td><td><p>1. Incorrect wiring.<\/p><p>2. Incorrect full open\/full close cam settings.<\/p><\/td><td><p>1. Use a mechanical switch to test actuator functionality. If it works, verify the control system output logic.<\/p><p>2. Check actuator\u2019s wiring against the wiring diagram.<\/p><p>3. Adjust the cam settings according to the &#8220;How to Set Switch-type Electric Valves&#8221; manual.<\/p><\/td><\/tr><tr><td><strong>Actuator stops in the middle of its stroke<\/strong><\/td><td><p>1. Valve is stuck.<\/p><p>2. Solid particles in the fluid medium causing valve blockage.<\/p><p>3. Incorrect full open\/full close block settings.<\/p><\/td><td><p>1. Check if the valve is stuck. Remove obstructions and retry after the actuator cools down from overload protection.<\/p><p>2. Inspect the fluid medium for solid particles. Remove any blockage and retry after cooling.<\/p><p>3. Adjust block settings according to the &#8220;How to Set Switch-type Electric Valves&#8221; manual.<\/p><\/td><\/tr><tr><td><strong>Cannot turn the actuator with the handwheel<\/strong><\/td><td><p>1. Solid particles in the fluid medium causing valve blockage.<\/p><p>2. Valve is stuck.<\/p><p>3. Actuator\u2019s reduction mechanism is damaged.<\/p><\/td><td><p>1. Check fluid medium for particles causing blockage. Remove obstructions and retry after cooling.<\/p><p>2. Inspect valve for any stuck parts. Remove blockage and retry.<\/p><p>3. If actuator cannot be turned by hand, remove it from the valve. If it still doesn&#8217;t turn, replace with a new actuator.<\/p><\/td><\/tr><tr><td><strong>No output from position feedback signal<\/strong><\/td><td><p>1. Incorrect switch wiring.<\/p><p>2. Incorrect full open\/full close cam settings.<\/p><p>3. Overcurrent causing damage to the position feedback signal switch.<\/p><\/td><td><p>1. Check wiring of the switch against the actuator\u2019s wiring diagram to ensure it is correct.<\/p><p>2. Verify full open\/full close cam is properly compressing the position feedback switch.<\/p><p>3. Measure the position feedback circuit to check if the switch is intact and properly connected.<\/p><\/td><\/tr><\/tbody><\/table><p>\u00a0<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-27fe35c elementor-widget elementor-widget-heading\" data-id=\"27fe35c\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<h1 class=\"elementor-heading-title elementor-size-default\">Please check if the operating conditions meet the parameter requirements.<\/h1>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-26c5591 elementor-widget elementor-widget-text-editor\" data-id=\"26c5591\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"\" data-start=\"3\" data-end=\"303\">Electric actuators may fail due to improper use or operating in incorrect conditions. To ensure long-term, trouble-free operation, the actuator must be used within the operating conditions specified in the product datasheet.<\/p><ul data-start=\"305\" data-end=\"1601\" data-is-last-node=\"\" data-is-only-node=\"\"><li class=\"\" data-start=\"305\" data-end=\"478\"><p class=\"\" data-start=\"307\" data-end=\"478\"><strong data-start=\"307\" data-end=\"332\">Power Supply Voltage:<\/strong> The supply voltage must be within the actuator&#8217;s rated operating voltage range. Overvoltage or undervoltage may reduce the actuator&#8217;s lifespan.<\/p><\/li><li class=\"\" data-start=\"479\" data-end=\"734\"><p class=\"\" data-start=\"481\" data-end=\"734\"><strong data-start=\"481\" data-end=\"506\">Power Supply Current:<\/strong> Since the motor&#8217;s starting current is significantly higher than the rated current, please ensure that the power supply can provide a current capacity at least 3 times the actuator&#8217;s rated current to ensure reliable operation.<\/p><\/li><li class=\"\" data-start=\"735\" data-end=\"950\"><p class=\"\" data-start=\"737\" data-end=\"950\"><strong data-start=\"737\" data-end=\"753\">Temperature:<\/strong> Ensure that the actuator operates within the rated temperature range. Operating the actuator outside the specified temperature range may cause malfunction, reduced lifespan, or eventual failure.<\/p><\/li><li class=\"\" data-start=\"951\" data-end=\"1385\"><p class=\"\" data-start=\"953\" data-end=\"1385\"><strong data-start=\"953\" data-end=\"969\">Environment:<\/strong> The DCL switch-type actuators are rated at IP67 for wind and rain protection. They are generally suitable for both indoor and outdoor use, providing protection against rain, splashes, and UV exposure (sunlight), which typically extends the product&#8217;s lifespan. Extremely corrosive environments may cause premature failure of electronic components. Do not use non-explosion-proof actuators in explosive atmospheres.<\/p><\/li><li class=\"\" data-start=\"1386\" data-end=\"1601\"><p class=\"\" data-start=\"1388\" data-end=\"1601\"><strong data-start=\"1388\" data-end=\"1403\">Duty Cycle:<\/strong> The duty cycle of the DCL switch-type actuator is 70% (42 seconds of operation per minute, with a required 18 seconds off). Exceeding a 70% duty cycle will trigger thermal protection for the motor.<\/p><\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-0f084a1 elementor-widget elementor-widget-heading\" data-id=\"0f084a1\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<h1 class=\"elementor-heading-title elementor-size-default\">Check if the wiring of the actuator is correct.<\/h1>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-82b97d5 elementor-widget elementor-widget-text-editor\" data-id=\"82b97d5\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"\" data-start=\"54\" data-end=\"264\">Ensure that all electrical connections are properly made according to the wiring diagram provided in the product manual. Incorrect wiring can lead to malfunction or damage to the actuator. Verify the following:<\/p><ul data-start=\"266\" data-end=\"686\" data-is-last-node=\"\" data-is-only-node=\"\"><li class=\"\" data-start=\"266\" data-end=\"347\"><p class=\"\" data-start=\"268\" data-end=\"347\">The power supply connections are properly secured and there are no loose wires.<\/p><\/li><li class=\"\" data-start=\"348\" data-end=\"455\"><p class=\"\" data-start=\"350\" data-end=\"455\">The control signal wiring is correctly connected, ensuring polarity and signal type are properly matched.<\/p><\/li><li class=\"\" data-start=\"456\" data-end=\"548\"><p class=\"\" data-start=\"458\" data-end=\"548\">The ground connection (if applicable) is properly established to avoid electrical hazards.<\/p><\/li><li class=\"\" data-start=\"549\" data-end=\"686\"><p class=\"\" data-start=\"551\" data-end=\"686\">Double-check the connection of any external components, such as limit switches or feedback devices, to ensure they are wired correctly.<\/p><\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-afb9d5d elementor-widget elementor-widget-template\" data-id=\"afb9d5d\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"template.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t<div class=\"elementor-template\">\n\t\t\t\t\t<div data-elementor-type=\"section\" data-elementor-id=\"10960\" class=\"elementor elementor-10960\" data-elementor-post-type=\"elementor_library\">\n\t\t\t\t\t<section class=\"elementor-section elementor-top-section elementor-element elementor-element-762f764e elementor-section-full_width elementor-section-height-default elementor-section-height-default\" data-id=\"762f764e\" data-element_type=\"section\" data-e-type=\"section\">\n\t\t\t\t\t\t<div class=\"elementor-container elementor-column-gap-default\">\n\t\t\t\t\t<div class=\"elementor-column elementor-col-100 elementor-top-column elementor-element elementor-element-66edc8c2\" data-id=\"66edc8c2\" data-element_type=\"column\" data-e-type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-1c53049 elementor-widget elementor-widget-heading\" data-id=\"1c53049\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<h2 class=\"elementor-heading-title elementor-size-default\">ENCENDIDO - APAGADO<\/h2>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/section>\n\t\t\t\t<section class=\"elementor-section elementor-top-section elementor-element elementor-element-26762140 elementor-section-full_width elementor-section-height-default elementor-section-height-default\" data-id=\"26762140\" data-element_type=\"section\" data-e-type=\"section\">\n\t\t\t\t\t\t<div class=\"elementor-container elementor-column-gap-default\">\n\t\t\t\t\t<div class=\"elementor-column elementor-col-50 elementor-top-column elementor-element elementor-element-8ee309f\" data-id=\"8ee309f\" data-element_type=\"column\" data-e-type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-3b29c61e elementor-widget elementor-widget-heading\" data-id=\"3b29c61e\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<p class=\"elementor-heading-title elementor-size-default\">A - Con 2 salidas de se\u00f1al de posici\u00f3n final activas<\/p>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-f40ad9 elementor-widget elementor-widget-image\" data-id=\"f40ad9\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img fetchpriority=\"high\" decoding=\"async\" width=\"400\" height=\"341\" src=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-a.webp\" class=\"attachment-full size-full wp-image-10324\" alt=\"\" srcset=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-a.webp 400w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-a-300x256.webp 300w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-a-14x12.webp 14w\" sizes=\"(max-width: 400px) 100vw, 400px\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-144c599d elementor-widget elementor-widget-text-editor\" data-id=\"144c599d\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<ul><li>Controlar el actuador para abrir o cerrar con K<\/li><li>El terminal de salida de la posici\u00f3n final APERTURA\/CIERRE enviar\u00e1 el evento como una se\u00f1al activa de 220 VCA cuando se alcance la posici\u00f3n final.<\/li><\/ul><p>\u00a0<\/p><p><strong>Detalles de conexi\u00f3n:<\/strong><\/p><ol><li>Conectar el neutro de la fuente de alimentaci\u00f3n de CA 85-220 V a P1.<\/li><li>Cambie la l\u00ednea AC85-220V a la posici\u00f3n CERRAR (P2) para cerrar la v\u00e1lvula.<\/li><li>Para abrir la v\u00e1lvula, coloque el interruptor de la l\u00ednea AC85-220V en la posici\u00f3n ABIERTA (P3).<\/li><li>P5 es el terminal de posici\u00f3n final ABIERTA que proporciona una fuente de CA de 220 V que se puede utilizar para encender una luz indicadora cuando el actuador alcanza la posici\u00f3n final de apertura.<\/li><li>P6 es el terminal de posici\u00f3n final ABIERTO que proporciona una fuente de CA de 220 V que se puede utilizar para encender una luz indicadora cuando el actuador alcanza la posici\u00f3n final de cierre.<\/li><li>Conecte la toma de tierra a P7.<\/li><\/ol>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t<div class=\"elementor-column elementor-col-50 elementor-top-column elementor-element elementor-element-b6785ff\" data-id=\"b6785ff\" data-element_type=\"column\" data-e-type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-3d9195a5 elementor-widget elementor-widget-heading\" data-id=\"3d9195a5\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<p class=\"elementor-heading-title elementor-size-default\">B - Con 2 interruptores de posici\u00f3n final pasivos<\/p>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-2f01f91f elementor-widget elementor-widget-image\" data-id=\"2f01f91f\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img decoding=\"async\" width=\"400\" height=\"348\" src=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-b.webp\" class=\"attachment-full size-full wp-image-10325\" alt=\"\" srcset=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-b.webp 400w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-b-300x261.webp 300w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-b-14x12.webp 14w\" sizes=\"(max-width: 400px) 100vw, 400px\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-7b2fa9cc elementor-widget elementor-widget-text-editor\" data-id=\"7b2fa9cc\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<ul><li>Controlar el actuador para abrir o cerrar con K<\/li><li>El terminal de salida de la posici\u00f3n final APERTURA\/CIERRE enviar\u00e1 el evento como una se\u00f1al pasiva cuando se alcance la posici\u00f3n final.<\/li><\/ul><p>\u00a0<\/p><p><strong>Detalles de conexi\u00f3n:<\/strong><\/p><ol><li>Conectar el neutro de la fuente de alimentaci\u00f3n de CA 85-220 V a P1.<\/li><li>Cambie la l\u00ednea AC85-220V a la posici\u00f3n CERRAR (P2) para cerrar la v\u00e1lvula.<\/li><li>Para abrir la v\u00e1lvula, coloque el interruptor de la l\u00ednea AC85-220V en la posici\u00f3n ABIERTA (P3).<\/li><li>P4 es el COM para la se\u00f1al de contacto pasivo de posici\u00f3n final ABIERTA\/CERRADA que normalmente est\u00e1 conectada a la se\u00f1al GND.<\/li><li>P5 es el terminal de posici\u00f3n final ABIERTA que se conectar\u00e1 a COM cuando el actuador alcance la posici\u00f3n final de apertura.<\/li><li>P6 es el terminal de cierre de posici\u00f3n final que se conectar\u00e1 a COM cuando el actuador alcance la posici\u00f3n final de cierre.<\/li><li>Conecte la toma de tierra a P7.<\/li><\/ol>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/section>\n\t\t\t\t<section class=\"elementor-section elementor-top-section elementor-element elementor-element-7c261b3e elementor-section-full_width elementor-section-height-default elementor-section-height-default\" data-id=\"7c261b3e\" data-element_type=\"section\" data-e-type=\"section\">\n\t\t\t\t\t\t<div class=\"elementor-container elementor-column-gap-default\">\n\t\t\t\t\t<div class=\"elementor-column elementor-col-50 elementor-top-column elementor-element elementor-element-571c4654\" data-id=\"571c4654\" data-element_type=\"column\" data-e-type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-796cfd57 elementor-widget elementor-widget-heading\" data-id=\"796cfd57\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<p class=\"elementor-heading-title elementor-size-default\">G - Motor de CC con 2 interruptores de posici\u00f3n final.<\/p>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-485d11ef elementor-widget elementor-widget-image\" data-id=\"485d11ef\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img decoding=\"async\" width=\"400\" height=\"391\" src=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-g.webp\" class=\"attachment-full size-full wp-image-10326\" alt=\"\" srcset=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-g.webp 400w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-g-300x293.webp 300w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-g-12x12.webp 12w\" sizes=\"(max-width: 400px) 100vw, 400px\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-6dea83a0 elementor-widget elementor-widget-text-editor\" data-id=\"6dea83a0\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<ul><li>Controla el actuador para que se abra o se cierre mediante la direcci\u00f3n de la alimentaci\u00f3n el\u00e9ctrica entre los terminales 1 y 2.<\/li><li>El terminal de salida de la posici\u00f3n final APERTURA\/CIERRE enviar\u00e1 el evento como una se\u00f1al pasiva cuando se alcance la posici\u00f3n final.<\/li><\/ul><p>\u00a0<\/p><p><strong>Detalles de conexi\u00f3n:<\/strong><\/p><ol><li>Conecte DC24V+ a P1 y DC24V- a P2 para cerrar la v\u00e1lvula.<\/li><li>Conecte DC24V+ a P2 y DC24V- a P1 para cerrar la v\u00e1lvula.<\/li><li>P3 es el COM para la se\u00f1al de contacto pasivo de posici\u00f3n final ABIERTA\/CERRADA que normalmente est\u00e1 conectada a la se\u00f1al GND.<\/li><li>P4 es el terminal de posici\u00f3n final ABIERTA que se conectar\u00e1 a COM cuando el actuador alcance la posici\u00f3n final de apertura.<\/li><li>P5 es el terminal de cierre de posici\u00f3n final que se conectar\u00e1 a COM cuando el actuador alcance la posici\u00f3n final de cierre.<\/li><li>Conecte la toma de tierra a P7.<\/li><\/ol>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t<div class=\"elementor-column elementor-col-50 elementor-top-column elementor-element elementor-element-2c13c7d1\" data-id=\"2c13c7d1\" data-element_type=\"column\" data-e-type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-5c3c94ac elementor-widget elementor-widget-heading\" data-id=\"5c3c94ac\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<p class=\"elementor-heading-title elementor-size-default\">Motor H - trif\u00e1sico de 380 VCA con 2 interruptores de posici\u00f3n final.<\/p>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-643529de elementor-widget elementor-widget-image\" data-id=\"643529de\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img loading=\"lazy\" decoding=\"async\" width=\"400\" height=\"412\" src=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-h.webp\" class=\"attachment-full size-full wp-image-10327\" alt=\"\" srcset=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-h.webp 400w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-h-291x300.webp 291w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-h-12x12.webp 12w\" sizes=\"(max-width: 400px) 100vw, 400px\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-13a7de73 elementor-widget elementor-widget-text-editor\" data-id=\"13a7de73\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<ul><li>Controlar el actuador para abrirlo o cerrarlo mediante un inversor externo para cambiar la fase de la alimentaci\u00f3n el\u00e9ctrica.<\/li><li>El terminal de salida de la posici\u00f3n final APERTURA\/CIERRE enviar\u00e1 el evento como una se\u00f1al pasiva cuando se alcance la posici\u00f3n final.<\/li><\/ul><p>\u00a0<\/p><p><strong>Detalles de conexi\u00f3n:<\/strong><\/p><ol><li>Al conectar la salida de un inversor trif\u00e1sico de 380 V CA a P1, P2 y P3, se puede controlar el actuador para abrir o cerrar la v\u00e1lvula cambiando el orden de las 3 fases.<\/li><li>Conectar el neutro de AC380V a N(P4).<\/li><li>El terminal P5 se utiliza para interactuar con un interruptor externo y controlar el orden trif\u00e1sico del inversor. Este terminal se conecta a N(P4) cuando el actuador no est\u00e1 en la posici\u00f3n final de CIERRE y se desconecta de N(P4) una vez que el actuador alcanza dicha posici\u00f3n.<\/li><li>El terminal P6 se utiliza para interactuar con un interruptor externo y controlar el orden trif\u00e1sico del inversor. Este terminal se conecta a N(P4) cuando el actuador no est\u00e1 en la posici\u00f3n final de APERTURA y se desconecta de N(P4) una vez que el actuador alcanza dicha posici\u00f3n.<\/li><li>P7 es el COM para la se\u00f1al de contacto pasivo de posici\u00f3n final ABIERTA\/CERRADA que normalmente est\u00e1 conectada a la se\u00f1al GND.<\/li><li>P8 es el terminal de posici\u00f3n final ABIERTA que se conectar\u00e1 a COM cuando el actuador alcance la posici\u00f3n final de apertura.<\/li><li>P9 es el terminal de cierre de posici\u00f3n final que se conectar\u00e1 a COM cuando el actuador alcance la posici\u00f3n final de cierre.<\/li><li>Conecte la toma de tierra a P12.<\/li><\/ol>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/section>\n\t\t\t\t<section class=\"elementor-section elementor-top-section elementor-element elementor-element-3f4fac5b elementor-section-full_width elementor-section-height-default elementor-section-height-default\" data-id=\"3f4fac5b\" data-element_type=\"section\" data-e-type=\"section\">\n\t\t\t\t\t\t<div class=\"elementor-container elementor-column-gap-default\">\n\t\t\t\t\t<div class=\"elementor-column elementor-col-100 elementor-top-column elementor-element elementor-element-60aed2ac\" data-id=\"60aed2ac\" data-element_type=\"column\" data-e-type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-3bd28765 elementor-widget elementor-widget-heading\" data-id=\"3bd28765\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<h2 class=\"elementor-heading-title elementor-size-default\">Avances y posicionamiento<\/h2>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/section>\n\t\t\t\t<section class=\"elementor-section elementor-top-section elementor-element elementor-element-8848769 elementor-section-full_width elementor-section-height-default elementor-section-height-default\" data-id=\"8848769\" data-element_type=\"section\" data-e-type=\"section\">\n\t\t\t\t\t\t<div class=\"elementor-container elementor-column-gap-default\">\n\t\t\t\t\t<div class=\"elementor-column elementor-col-33 elementor-top-column elementor-element elementor-element-1c17c3e\" data-id=\"1c17c3e\" data-element_type=\"column\" data-e-type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-35fbead8 elementor-widget elementor-widget-heading\" data-id=\"35fbead8\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<p class=\"elementor-heading-title elementor-size-default\">F - Con una unidad de posicionamiento<\/p>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-1ac5eaa3 elementor-widget elementor-widget-image\" data-id=\"1ac5eaa3\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img loading=\"lazy\" decoding=\"async\" width=\"400\" height=\"316\" src=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-f.webp\" class=\"attachment-full size-full wp-image-10321\" alt=\"\" srcset=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-f.webp 400w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-f-300x237.webp 300w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-f-15x12.webp 15w\" sizes=\"(max-width: 400px) 100vw, 400px\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-80dac2d elementor-widget elementor-widget-text-editor\" data-id=\"80dac2d\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<ul><li>Controlar el actuador para abrir o cerrar con K<\/li><li>La posici\u00f3n de la v\u00e1lvula en tiempo real se enviar\u00e1 como una se\u00f1al de 4-20 mA.<\/li><\/ul><p>\u00a0<\/p><p><strong>Detalles de conexi\u00f3n:<\/strong><\/p><ol><li>Conecte la l\u00ednea de alimentaci\u00f3n de CA 85-220 V a L y el neutro a N.<\/li><li>Para cerrar la v\u00e1lvula, coloque el interruptor de la l\u00ednea AC85-220V en la posici\u00f3n CERRAR (P2).<\/li><li>Para abrir la v\u00e1lvula, coloque el interruptor de la l\u00ednea AC85-220V en la posici\u00f3n ABIERTA (P3).<\/li><li>Conectar la salida -\/+ al sistema para enviar la posici\u00f3n de la v\u00e1lvula en tiempo real.<\/li><\/ol>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t<div class=\"elementor-column elementor-col-33 elementor-top-column elementor-element elementor-element-48cb89dd\" data-id=\"48cb89dd\" data-element_type=\"column\" data-e-type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-82392c9 elementor-widget elementor-widget-heading\" data-id=\"82392c9\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<p class=\"elementor-heading-title elementor-size-default\">C - Con un potenci\u00f3metro de 1 k\u03a9\/500 \u03a9<\/p>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-7d24d552 elementor-widget elementor-widget-image\" data-id=\"7d24d552\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img loading=\"lazy\" decoding=\"async\" width=\"400\" height=\"380\" src=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-c.webp\" class=\"attachment-full size-full wp-image-10322\" alt=\"\" srcset=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-c.webp 400w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-c-300x285.webp 300w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-c-13x12.webp 13w\" sizes=\"(max-width: 400px) 100vw, 400px\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-11e65789 elementor-widget elementor-widget-text-editor\" data-id=\"11e65789\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<ul><li>Controlar el actuador para abrir o cerrar con K<\/li><li>La posici\u00f3n de la v\u00e1lvula en tiempo real se enviar\u00e1 como un valor de resistencia del potenci\u00f3metro.<\/li><\/ul><p>\u00a0<\/p><p><strong>Detalles de conexi\u00f3n:<\/strong><\/p><ol><li>Conectar el neutro de la fuente de alimentaci\u00f3n de CA 85-220 V a P1.<\/li><li>Cambie la l\u00ednea AC85-220V a la posici\u00f3n CERRAR (P2) para cerrar la v\u00e1lvula.<\/li><li>Para abrir la v\u00e1lvula, coloque el interruptor de la l\u00ednea AC85-220V en la posici\u00f3n ABIERTA (P3).<\/li><li>P4 es el lado bajo del potenci\u00f3metro que normalmente est\u00e1 conectado a la tierra de se\u00f1al (GND).<\/li><li>Conectando la entrada de se\u00f1al del sistema de control a P5. El valor de resistencia entre P4 y P5 aumentar\u00e1 a medida que el actuador abra la v\u00e1lvula, mientras que el valor entre P5 y P6 disminuir\u00e1.<\/li><li>P6 es el lado de alta tensi\u00f3n del potenci\u00f3metro que normalmente est\u00e1 conectado a la alimentaci\u00f3n de la se\u00f1al.<\/li><li>Conecte la toma de tierra a P7.<\/li><\/ol>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t<div class=\"elementor-column elementor-col-33 elementor-top-column elementor-element elementor-element-2eb5f8cd\" data-id=\"2eb5f8cd\" data-element_type=\"column\" data-e-type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-704d6f35 elementor-widget elementor-widget-heading\" data-id=\"704d6f35\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<p class=\"elementor-heading-title elementor-size-default\">D - Con un potenci\u00f3metro y retroalimentaci\u00f3n de posici\u00f3n final.<\/p>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-65ba6b3f elementor-widget elementor-widget-image\" data-id=\"65ba6b3f\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img loading=\"lazy\" decoding=\"async\" width=\"400\" height=\"437\" src=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-d.webp\" class=\"attachment-full size-full wp-image-10323\" alt=\"\" srcset=\"https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-d.webp 400w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-d-275x300.webp 275w, https:\/\/dclcontrols.com\/wp-content\/uploads\/2025\/02\/dcl-actuator-interface-diagram-d-11x12.webp 11w\" sizes=\"(max-width: 400px) 100vw, 400px\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-64fc0e34 elementor-widget elementor-widget-text-editor\" data-id=\"64fc0e34\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<ul><li>Controlar el actuador para abrir o cerrar con K<\/li><li>La posici\u00f3n de la v\u00e1lvula en tiempo real se enviar\u00e1 como un valor de resistencia del potenci\u00f3metro.<\/li><li>El terminal de salida de la posici\u00f3n final APERTURA\/CIERRE enviar\u00e1 el evento como una se\u00f1al pasiva cuando se alcance la posici\u00f3n final.<\/li><\/ul><p>\u00a0<\/p><p><strong>Detalles de conexi\u00f3n:<\/strong><\/p><ol><li>Conectar el neutro de la fuente de alimentaci\u00f3n de CA 85-220 V a P1.<\/li><li>Cambie la l\u00ednea AC85-220V a la posici\u00f3n CERRAR (P2) para cerrar la v\u00e1lvula.<\/li><li>Para abrir la v\u00e1lvula, coloque el interruptor de la l\u00ednea AC85-220V en la posici\u00f3n ABIERTA (P3).<\/li><li>P4 es el COM para la se\u00f1al de contacto pasivo de posici\u00f3n final ABIERTA\/CERRADA que normalmente est\u00e1 conectada a la se\u00f1al GND.<\/li><li>P5 es el terminal de posici\u00f3n final ABIERTA que se conectar\u00e1 a COM cuando el actuador alcance la posici\u00f3n final de apertura.<\/li><li>P6 es el terminal de cierre de posici\u00f3n final que se conectar\u00e1 a COM cuando el actuador alcance la posici\u00f3n final de cierre.<\/li><li>P7 es el lado bajo del potenci\u00f3metro que normalmente est\u00e1 conectado a la tierra de se\u00f1al (GND).<\/li><li>Conectando la entrada de se\u00f1al del sistema de control a P8. El valor de resistencia entre P7 y P8 aumentar\u00e1 a medida que el actuador abra la v\u00e1lvula, mientras que el valor entre P8 y P9 disminuir\u00e1.<\/li><li>P9 es el lado de alta tensi\u00f3n del potenci\u00f3metro que normalmente est\u00e1 conectado a la alimentaci\u00f3n de la se\u00f1al.<\/li><li>Conecte la toma de tierra a P12.<\/li><\/ol>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/section>\n\t\t\t\t<section class=\"elementor-section elementor-top-section elementor-element elementor-element-472b66b9 elementor-section-full_width elementor-section-height-default elementor-section-height-default\" data-id=\"472b66b9\" data-element_type=\"section\" data-e-type=\"section\">\n\t\t\t\t\t\t<div class=\"elementor-container elementor-column-gap-default\">\n\t\t\t\t\t<div class=\"elementor-column elementor-col-100 elementor-top-column elementor-element elementor-element-1cfb59fd\" data-id=\"1cfb59fd\" data-element_type=\"column\" data-e-type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-7a09a4a6 elementor-widget elementor-widget-text-editor\" data-id=\"7a09a4a6\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p>Nota:<\/p><ul><li>El circuito dentro del recuadro punteado es el circuito interno del actuador. El circuito exterior muestra la conexi\u00f3n el\u00e9ctrica para el funcionamiento del actuador.<\/li><li>Si tiene otros requisitos espec\u00edficos sobre la conexi\u00f3n del circuito, no dude en ponerse en contacto con nuestro servicio de asistencia t\u00e9cnica.\u00a0<\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/section>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>","protected":false},"excerpt":{"rendered":"<p>This guide applies to the switch-type actuators of the DCL explosion-proof series, standard series, and quick-open series. The models are as follows: Weather-proof Actuator: DCL-05, DCL-10, DCL-20, DCL-40, DCL-60, DCL-100, DCL-160, DCL-250Explosion-Proof Actuator: DCL-Ex05, DCL-Ex10, DCL-Ex20, DCL-Ex40, DCL-Ex60Quick-Turn Actuator: DCL-K05, DCL-K10, DCL-K20, DCL-K40, DCL-K100 Common Faults and Troubleshooting Methods \u00a0 Fault Possible Causes Troubleshooting Methods [&hellip;]<\/p>","protected":false},"author":1,"featured_media":10962,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":true,"footnotes":""},"categories":[103],"tags":[53],"class_list":["post-6032","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-mr-actuator","tag-actuator"],"acf":[],"_links":{"self":[{"href":"https:\/\/dclcontrols.com\/es_cl\/wp-json\/wp\/v2\/posts\/6032","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/dclcontrols.com\/es_cl\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/dclcontrols.com\/es_cl\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/dclcontrols.com\/es_cl\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/dclcontrols.com\/es_cl\/wp-json\/wp\/v2\/comments?post=6032"}],"version-history":[{"count":0,"href":"https:\/\/dclcontrols.com\/es_cl\/wp-json\/wp\/v2\/posts\/6032\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/dclcontrols.com\/es_cl\/wp-json\/wp\/v2\/media\/10962"}],"wp:attachment":[{"href":"https:\/\/dclcontrols.com\/es_cl\/wp-json\/wp\/v2\/media?parent=6032"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/dclcontrols.com\/es_cl\/wp-json\/wp\/v2\/categories?post=6032"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/dclcontrols.com\/es_cl\/wp-json\/wp\/v2\/tags?post=6032"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}